Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop M
Sequence Number 2
Notes
Date Text
2001-05-18 00:00:00*******************DENIED***************
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS
 COMMON/ASSEMBLY AREAS IN BUILDING.
 (AS PER ASHRAE 62-89)
  
 2.PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2.
  
 3.PLEASE SHOW COMPLIANCE WITH FLORIDA
 ENERGY CODE FOR BUILDING CON-
 STRUCTION SECTION 101.5.8, #1 - FOR
 CONDITIONED PARKING GARAGES.
  
 4.DRYER SHAFTS HAVE LIMITED CLEAN
 OUTS, HOW IS COMBUSTIBLE LINT
 REMOVED FROM DRYER SHAFTS.
  
 5.THE GAS METER PROVIDED FOR PLAN
 REVIEW, HAS NO UL OR FM APPROVAL
 ON MANUFACTURE SUBMITTAL DATA.
  
 5.NO CUT SHEETS PROVIDED FOR GAS
 FIREPLACES OR THE APPARTMENT
 KITCHEN HOODS.PROVIDE INFORMATION
 ON FLUE PIPE (CONSTRUCTION, SIZE
 AND TERMINATION).
  
 6.PLEASE EXPLAIN DISCREPANCY BETWEEN
 AIRWAY ROOM PLANS.AIRWAY ON
 "A" DRAWINGS INDICATES A DOOR AND
 "M" DRAWINGS NO DOOR IS DEPICTED.
  
 7.PROVIDE STAIRWELL PRESSURIZATION
 CALCULATIONS.
  
 8.PLEASE PROVIDE INFORMATION ON THE
 "FAN ROOMS"ON THE ROOF.
  
 9.PROVIDE INFORMATION ON "SHAFT
 GRILLE ABOVE" LOCATED IN THE
 GARAGE.
  
 10.PLEASE PROVIDE CALCULATIONS FOR
 VENTILATION IN PARKING GARAGE, SHOW
 COMPLIANCE WITH 1997 SBC 411.4.2.
  
  
 NOTE:NO COMBUSTIBLES ABOVE CEILING IF
 USED AS RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.