| 2001-05-18 00:00:00 | *******************DENIED*************** |
| | |
| | 1.PROVIDE OUTSIDE AIR CALCULATIONS |
| | COMMON/ASSEMBLY AREAS IN BUILDING. |
| | (AS PER ASHRAE 62-89) |
| | |
| | 2.PROVIDE AIR BALANCE SCHEDULE AS PER |
| | 1997 SMC 501.2. |
| | |
| | 3.PLEASE SHOW COMPLIANCE WITH FLORIDA |
| | ENERGY CODE FOR BUILDING CON- |
| | STRUCTION SECTION 101.5.8, #1 - FOR |
| | CONDITIONED PARKING GARAGES. |
| | |
| | 4.DRYER SHAFTS HAVE LIMITED CLEAN |
| | OUTS, HOW IS COMBUSTIBLE LINT |
| | REMOVED FROM DRYER SHAFTS. |
| | |
| | 5.THE GAS METER PROVIDED FOR PLAN |
| | REVIEW, HAS NO UL OR FM APPROVAL |
| | ON MANUFACTURE SUBMITTAL DATA. |
| | |
| | 5.NO CUT SHEETS PROVIDED FOR GAS |
| | FIREPLACES OR THE APPARTMENT |
| | KITCHEN HOODS.PROVIDE INFORMATION |
| | ON FLUE PIPE (CONSTRUCTION, SIZE |
| | AND TERMINATION). |
| | |
| | 6.PLEASE EXPLAIN DISCREPANCY BETWEEN |
| | AIRWAY ROOM PLANS.AIRWAY ON |
| | "A" DRAWINGS INDICATES A DOOR AND |
| | "M" DRAWINGS NO DOOR IS DEPICTED. |
| | |
| | 7.PROVIDE STAIRWELL PRESSURIZATION |
| | CALCULATIONS. |
| | |
| | 8.PLEASE PROVIDE INFORMATION ON THE |
| | "FAN ROOMS"ON THE ROOF. |
| | |
| | 9.PROVIDE INFORMATION ON "SHAFT |
| | GRILLE ABOVE" LOCATED IN THE |
| | GARAGE. |
| | |
| | 10.PLEASE PROVIDE CALCULATIONS FOR |
| | VENTILATION IN PARKING GARAGE, SHOW |
| | COMPLIANCE WITH 1997 SBC 411.4.2. |
| | |
| | |
| | NOTE:NO COMBUSTIBLES ABOVE CEILING IF |
| | USED AS RETURN AIR PLENUM. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT |
| | PATTY KRAUSS AT 659-8096 EXT. 8388. |