Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-05-24 00:00:001) GAS METER PRODUCT APPROVAL DISPLAYS
 NO UL OR FM APPROVALS.
 2) NO PLAN REVIEW COMMENTS REGARDING GAS
 INSTALLATION BY GAS COMPANY.
 3) DRYER SHAFTS NOT PROVIDED WITH ENOUGH
 CLEAN-OUT LOCATIONS FOR THE REMOVAL
 OF COMBUSTIBLE LINT. ONLY TWO ARE SHOWN
 AT CHANGE OF DIRECTIONS.
 4) EXPLAIN DOORS AND BALCONIES.
 5) PLEASE PROVIDE PERCENTAGE OF OPENINGS
 PER EXTERIOR WALLS IN PARKING GARAGE.
 PLEASE INDICATE ON PLANS WHETHER THE
 PARKING GARAGE IS CONSIDERED OPEN OR
 CLOSED.
 6) TRASH CHUTES ARE NOT PERMITTED TO
 OPEN INTO THE ELEVATOR EQUIPMENT ROOMS.
 THESE CHUTES ARE TO TERMINATE INTO THE
 OPEN AIR WITH A MINIMUM OF THREE FEET
 ABOVE THE ROOF. PLEASE PROVIDE DETAILS
 FOR TRASH CHUTE TERMINATIONS.
 7) HOW IS ACCESS PROVIDED TO GAS METER
 AND GAS SHUT-OFF VALVE.
 8) PLEASE EXPLAIN HOW PRODUCTS OF
 COMBUSTION WILL NOT ENTER THE
 STAIRTOWERS WHERE OPENINGS ARE PRESENT
 NEAR THE DUAL BALCONIES. THIS OFFICE
 DOES UNDERSTAND THAT THESE MATERIALS
 WILL RISE, BUT WHAT PREVENTS ANY
 CONTAMINATION.
 9) PLEASE INDICATE WHERE THE ELEVATOR
 LOCATED IN THE NORTHWEST CORNER OF
 THE PROPERTY TRAVELS TO.
 10) PLEASE INDICATE EMERGENCY LIGHTING
 IN GARAGE.
 11) PLEASE EXPLAIN GARAGE EXHAUST FANS
 ON/OFF CONTROLS IN FIRE COMMAND ROOM.
 12) PLEASE EXPLAIN ELEVATOR SECURITY
 SWITCHES.
 13) HOW DOES BUILDING SECURITY FEATURES
 AFFECT EXITING.
 14) EXIT DOOR ON PAGE E.1.1.1 NEAR
 GENERATOR ROOM DOES NOT SWING IN THE
 DIRECTION OF EXIT TRAVEL.
 15) PLEASE NOTE ON THE PLANS THAT A
 MINIMUM OF SIX AIR CHANGES ARE REQUIRED
 WITHIN THE CLOSED PARKING GARAGE. GARAGE
 VENTILATION FANS ARE TO BE PROVIDED
 WITH EMERGENCY POWER.
 16) NO LITERATURE PROVIDED BY BCBE OR
 CIVIL ENGINEERS. NO LITERATURE PROVIDED
 FOR GAS FIREPLACES.
 17) PLEASE INDICATE THE WIDTH OF THE
 OPENINGS AT THE STAIRS NEAR THE
 BALCONIES.
  
 WRITER DID SPEAK TO MIKE GOTWALT AND
 OBTAINED SOME ANSWERS TO SOME OF THESE
 PLAN REVIEW COMMENTS HOWEVER WRITER WAS
 NOT COMPLETED.
  
 PLEASE INDICATE HOW SMOKE COULD BE
 REMOVED FROM THE CORE AREAS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910