| 2001-05-30 00:00:00 | E6.1.1 SHOWS RISER WITH NO WIRE SIZES | | | AND/OR CONDUIT SIZES. | | | | | | NEED A SCHEDULE FOR MCC SIZE OF WIRES TO | | | THE DIFFERNET LOADS, SHOW SIZES OF FUSE | | | OR CIRCUIT BREAKERS TO LOADS FED BY MCC | | | | | | PLEASE SHOW HOW IN THE PENTHOUSES THAT | | | ONE METER WILL BE FEEDING THREE PANELS | | | FOR UNITS F(2), G , AND JSUBMIT RISER | | | | | | PLANS ARE GENERALY IN GOOD SHAPE BUT | | | THERISER DIAGRAM IS VERY CONFUSING, A | | | ONE | | | LINE FOR THE NORMAL AND ONE FOR THE | | | EMERGENCY RISERS WOULD BE GREAT SHOWING | | | WHATFEEDS WHAT WITHOUT HAVING TO GO TO | | | SEVER | | | AL PAGES TO GET THE INFORMATION! |
|