Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop E
Sequence Number 2
Notes
Date Text
2001-05-30 00:00:00E6.1.1 SHOWS RISER WITH NO WIRE SIZES
 AND/OR CONDUIT SIZES.
  
 NEED A SCHEDULE FOR MCC SIZE OF WIRES TO
 THE DIFFERNET LOADS, SHOW SIZES OF FUSE
 OR CIRCUIT BREAKERS TO LOADS FED BY MCC
  
 PLEASE SHOW HOW IN THE PENTHOUSES THAT
 ONE METER WILL BE FEEDING THREE PANELS
 FOR UNITS F(2), G , AND JSUBMIT RISER
  
 PLANS ARE GENERALY IN GOOD SHAPE BUT
 THERISER DIAGRAM IS VERY CONFUSING, A
 ONE
 LINE FOR THE NORMAL AND ONE FOR THE
 EMERGENCY RISERS WOULD BE GREAT SHOWING
 WHATFEEDS WHAT WITHOUT HAVING TO GO TO
 SEVER
 AL PAGES TO GET THE INFORMATION!