Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop B
Sequence Number 2
Notes
Date Text
2001-05-29 00:00:00PLEASE PROVIDE A RECENT PROPERTY SURVEY
  
 SHOW HOW HURRICANE MISSILE IMPACT
 RESISTANCE FOR THE GLAZED EXTERIOR
 PORTIONS WILL BE ACCOMPLISHED.
  
 THE PLANS MUST HAVE THE IMPACT FEE STAMP
 ON THEM.
  
 PROVIDE TEST DATA FOR THE WINDOWS, DOORS
 AND ROOF COVERING.
  
 UNIT TYPES E AND G DO NOT COMPLY WITH
 SBC 1004.1.4
  
 ENTRY VESTIBULES E32 AND G40 DO NOT
 COMPLY WITH THE ELEVATOR LOBBY
 SEPARATION REQUIERMENTS OF SBC 412.6.
  
 THE USE OF WOOD WITHIN THE CONSTRUCTION
 OF TYPE I & II BUILDINGS IS REQUIED TO
 BE FIRE RETARDANT TREATED.
  
 CITING A CODE SECTION IS NOT ACCEPTABLE
 IN LIEU OF SPECIFIC DESIGN INFORMATION
 WITH REGARDS TO THE HAND AND GUARD
 RAILS.
  
 SHOW HOW DAMP PROOFING WILL BE
 ACCOMPLISHED ON THE WEST SIDE OF THE
 GARAGE.SEESBC 1814.3.
  
 THE DESIGNERS RESPONSES TO THE FIRST
 CHECKLIST WERE REVIEWED AND THESE ARE
 THE SUBSEQUENT FINDINGS.