| Plan Review Notes For Permit 01030147 |
| Permit Number |
01030147 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-05-29 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY | | | | | | SHOW HOW HURRICANE MISSILE IMPACT | | | RESISTANCE FOR THE GLAZED EXTERIOR | | | PORTIONS WILL BE ACCOMPLISHED. | | | | | | THE PLANS MUST HAVE THE IMPACT FEE STAMP | | | ON THEM. | | | | | | PROVIDE TEST DATA FOR THE WINDOWS, DOORS | | | AND ROOF COVERING. | | | | | | UNIT TYPES E AND G DO NOT COMPLY WITH | | | SBC 1004.1.4 | | | | | | ENTRY VESTIBULES E32 AND G40 DO NOT | | | COMPLY WITH THE ELEVATOR LOBBY | | | SEPARATION REQUIERMENTS OF SBC 412.6. | | | | | | THE USE OF WOOD WITHIN THE CONSTRUCTION | | | OF TYPE I & II BUILDINGS IS REQUIED TO | | | BE FIRE RETARDANT TREATED. | | | | | | CITING A CODE SECTION IS NOT ACCEPTABLE | | | IN LIEU OF SPECIFIC DESIGN INFORMATION | | | WITH REGARDS TO THE HAND AND GUARD | | | RAILS. | | | | | | SHOW HOW DAMP PROOFING WILL BE | | | ACCOMPLISHED ON THE WEST SIDE OF THE | | | GARAGE.SEESBC 1814.3. | | | | | | THE DESIGNERS RESPONSES TO THE FIRST | | | CHECKLIST WERE REVIEWED AND THESE ARE | | | THE SUBSEQUENT FINDINGS. |
|