Plan Review Notes
Plan Review Notes For Permit 01030147
Permit Number 01030147
Review Stop E
Sequence Number 19
Notes
Date Text
2003-02-18 00:00:00************** UNSAT ***************
  
 PLANS HAVE BEEN SUBMITTED FOR FINAL
 "AS-BUILT" REVISED DRAWINGS, PLEASE
 SEE THE FOLLOWING NOTES.
  
 1)NOTE: PLEASE SEE UNIT 301, EQUIPMENT
 GROUNDING CONDUCTOR SHOWN AS ALUM.
 AS PER LOCAL AMENDMENTS, 310-2 ALUM
 SHALL NOT BE USED FOR GROUNDING. PLEASE
 NOTE, ALL OTHER UNITS ARE SHOWN AS CU.
  
 2)NOTE: PLEASE SEE UNIT #803, PLEASE
 SEE LOADS SHOWN ON 15A BRKRS. MAX VA
 ON 15A IS 1440. (80%) THIS HAS BEEN
 CORRECTED ON ALL OF THE OTHER SHEETS
 SUBMITTED.
  
  
 3)NOTE: PLEASE SEE LOADS THAT DO NOT
 CORRELATE. MAIN PANELS SHOW ONE LOAD
 AND SUB PANELS SHOW DIFFERENT LOAD.
 UNIT 1001,603, PH-3.
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372