| Plan Review Notes For Permit 01030147 |
| Permit Number |
01030147 |
|
| Review Stop |
E |
| Sequence Number |
19 |
|
| Notes |
| Date |
Text |
| 2003-02-18 00:00:00 | ************** UNSAT *************** | | | | | | PLANS HAVE BEEN SUBMITTED FOR FINAL | | | "AS-BUILT" REVISED DRAWINGS, PLEASE | | | SEE THE FOLLOWING NOTES. | | | | | | 1)NOTE: PLEASE SEE UNIT 301, EQUIPMENT | | | GROUNDING CONDUCTOR SHOWN AS ALUM. | | | AS PER LOCAL AMENDMENTS, 310-2 ALUM | | | SHALL NOT BE USED FOR GROUNDING. PLEASE | | | NOTE, ALL OTHER UNITS ARE SHOWN AS CU. | | | | | | 2)NOTE: PLEASE SEE UNIT #803, PLEASE | | | SEE LOADS SHOWN ON 15A BRKRS. MAX VA | | | ON 15A IS 1440. (80%) THIS HAS BEEN | | | CORRECTED ON ALL OF THE OTHER SHEETS | | | SUBMITTED. | | | | | | | | | 3)NOTE: PLEASE SEE LOADS THAT DO NOT | | | CORRELATE. MAIN PANELS SHOW ONE LOAD | | | AND SUB PANELS SHOW DIFFERENT LOAD. | | | UNIT 1001,603, PH-3. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|