| Plan Review Notes For Permit 01030147 |
| Permit Number |
01030147 |
|
| Review Stop |
E |
| Sequence Number |
16 |
|
| Notes |
| Date |
Text |
| 2003-01-14 00:00:00 | NOTES TO FOLLOW. | | | ********** NOTES/PROVISO *********** | | | | | | BEFORE MARCH 1ST, 2003 | | | | | | PLEASE NOTE, THESE ARE MOSTLY THE SAME | | | NOTES FOR ALL OF THE FOLLOWING UNITS. | | | PLEASE NOTE SOME UNITS MAY BE DIFFERENT | | | DUE TO MODEL AND OWNER CHANGES. | | | | | | 1)NOTE: PLEASE CORRELATE ALL LOAD | | | CALCULATIONS AND PANEL SCHEDULES PER | | | UNIT. PLEASE SEE LOADS SHOWN ON | | | SUB-PANELS, THESE DO NOT CORRELATE WITH | | | MAIN PANEL LOAD SCHEDULE. | | | | | | 2)NOTE: PLEASE NOTE SOME UNITS APPEAR TO | | | HAVE RECEPTS MORE THAN 3' FROM SINKS, | | | PER 210-52D. | | | | | | 3)NOTE: PLEASE ALSO NOTE SOME UNITS ARE | | | MISSING OUTLETS IN ORDER TO MEET 210-52. | | | | | | 4)NOTE: PLEASE NOTE, ORIG PLANS WERE | | | SUBMITTED FOR MOSTLY GAS APPL/DRYERS, | | | DUE TO MANY CHANGES IN LOADS TO UNIT | | | PLANS. PLEASE RECONFIGURE LOAD CALCULAT- | | | IONS FOR BLDG SERVICE AND SUBMIT REVISED | | | PLAN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE 03/01/03. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | UNITS, 603,604,804,1003,1004, | | | 704,904 702,703 |
|