2003-01-07 00:00:00************* UNSAT *****************
 6TH FLR UNIT 601 REV.
  
 1)NOTE: PLEASE SEE OVERLOADING OF
 CIRCUITS IN PANEL.
 PLEASE BREAK DOWN LOAD CALACULATIONS
 TO SEE IF 200AQ PANEL IS ADEQUATE FOR
 UNIT. LOAD IS SHOWN AT OVER 345 A'S???
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  