| Plan Review Notes For Permit 01030147 |
| Permit Number |
01030147 |
|
| Review Stop |
E |
| Sequence Number |
15 |
|
| Notes |
| Date |
Text |
| 2003-01-07 00:00:00 | ************* UNSAT ***************** | | | 6TH FLR UNIT 601 REV. | | | | | | 1)NOTE: PLEASE SEE OVERLOADING OF | | | CIRCUITS IN PANEL. | | | PLEASE BREAK DOWN LOAD CALACULATIONS | | | TO SEE IF 200AQ PANEL IS ADEQUATE FOR | | | UNIT. LOAD IS SHOWN AT OVER 345 A'S??? | | | | | | PLEASE SUBMITTHE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|