| Plan Review Notes For Permit 01030147 |
| Permit Number |
01030147 |
|
| Review Stop |
E |
| Sequence Number |
14 |
|
| Notes |
| Date |
Text |
| 2002-12-27 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE REVISED PANEL SCHED. | | | LOAD EXCEEDS RATING OF EQUIPMENT.PLEASE | | | ALSO NOTE, LOAD CALCS NEED TO CORRELATE | | | TO ART 220 OFTHE NEC. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|