| Plan Review Notes For Permit 01030147 |
| Permit Number |
01030147 |
|
| Review Stop |
E |
| Sequence Number |
12 |
|
| Notes |
| Date |
Text |
| 2002-12-13 00:00:00 | UNIT 702 CIRCUIT #3 IS OVERLOADED PER | | | PLAN.LOAD ON SUB PANEL NOT THE SAME | | | WHEN PUT INTO MAIN PANEL. | | | | | | UNIT 703 SAME WITHN SUB PANEL, CIRCUIT | | | #4,8 IN C2 ARE OVERLOADED PER PLAN. | | | | | | UNIT 704 SAME WITH PANELS, CIRCUIT #6 | | | IN D2 IS OVERLOADED PER PLAN. | | | | | | UNIT 904SAME WITH PANELS, CIRCUIT #6 IS | | | OVERLOADED PER PLAN. |
|