| Notes |
| Date |
Text |
| 2003-01-16 00:00:00 | REVISIONS DATED 12/13/02 MARKED SK1 AND | | | RE: A.4.3.1. | | | | | | PROVIDE A FIRE DESIGN NUMBER FOR THE | | | TWO HR RATED CEILING ON THE STAIR | | | CONNECTOR TO DEMONSTRATE COMPLIANCE | | | WITH FBC 704.2.1.2. | | | | | | SK3 DATED 11/26/2000 "NEW DETAIL" | | | EMERGENCY OVERFLOW SCUPPER.WHAT | | | VOLUME OF WATER IS ANTICIPATED TO FLOW | | | THROUGH THE UNDEFINED FIBERGLASS SCREEN | | | AREA? | | | | | | SK4 DATED 11/26/2000 AND NOTED A.4.12.1 | | | AND SK5 DATED 11/26/2000 AND NOTED | | | A.4.15.1.THE CHANGE FROM ROOF AREA TO | | | BALCONY REQUIRES ADDITIONAL DETAILS FOR | | | THE ALUM GUARD RAIL, FLOOR SURFACE TO BE | | | USED, AND COMPLIANCE WITH THE FAIR | | | HOUSING ACT. |
|