| Date |
Text |
| 2001-03-25 00:00:00 | PLUMBING PLAN REVIEWDENIED |
| | CODE REFERENCE SPC 94,SGC 97. |
| | (1A)SHT C-4 ALL SITE WATER,SANITARY |
| | SEWER TO COMPLY WITH CITY OF W PALM BCH. |
| | UTILITY STDS. |
| | (B) DOMESTIC WATER TO DOCK,BACK FLOW |
| | PREVENTER REQ. SEC. 606 |
| | (C)SHOW LOCATION OF GAS SERVICE & METER. |
| | (2A)SHT P001 PROVIDE A COMPLETE LIST OF |
| | ALL ABBREVATIONS USED ON PLBG PLANS. |
| | (B) ELEVATOR SUMP,SHOW DISCHARGE TERMIN- |
| | ATION, IF HYDURALIC,OIL INTERCEPTOR REQ, |
| | WITH AN INDIRECT WASTE CONNECTION. |
| | (C) PLANS DO NOT INCLUDE SHTS POO2,P103, |
| | P203,P204,P404,P504,P604,P703,P803,P903. |
| | (3) SHT P101 CAR WASH,SEC 1004.6 SAND |
| | INTERCEPTOR REQ. |
| | (4) SHT P103 COMPLY WITH SEC 607 WATER |
| | SUPPLY SIZING, SHOW CALCULATIONS FOR |
| | SIZING THE DEMAND LOAD FOR THE ENTIRE |
| | SYSTEM, BASED ON DFU. |
| | (5) SEC 104.2.4 STRUCTURAL AND FIRE |
| | RESISTANCE INTEGRITY. UL LISTING FOR ALL |
| | RATED FLOOR,WALL PENETRATIONS. |
| | (6) SEC 104.2 SUBMITALS FOR ALL MATERIAL |
| | AND SPECIFICATIONS. |
| | (7) SEC 104.2 DRAWINGS:PROVIDE ISOMETRIC |
| | DRAWINGS FOR WATER & DRAIN WASTE,VENT |
| | SYSTEM, DWV SHOW SIZING CALCULATIONS. |
| | (8) SEC 104.2 PROVIDE A GAS ISOMETRIC, |
| | SEE ATTACHED REQUIRMENTS FOR GAS PERMIT |
| | DRAWINGS & APPLICATION. |
| | (9) SHT P306 ROOF & SCUPPER DRAINS SEC. |
| | 1109.1 & APPEX "A",SEC 1108.3 VERTIAL |
| | WALLS,SHOW AREA DRAINED IN SQUARE FEET |
| | PLUS 1/2 THE VERTICAL AREA OF WALLS & |
| | PARAPETS,ISOMETRIC DRAWING OF SYSTEM. |
| | (10) SEC 1109 SECONDARYROOF DRAINS: |
| | PROVIDE CALCULATIONS FOR SIZING,LOCATION |
| | OF THE SECONDARY DRAINS. |
| | (11) ALL KITCHENS & BATH ROOMS SHALL |
| | COMPLY WITH THE U S DEPT OF HOUSING AND |
| | URBAN DEVELOPMENT (HUD) FAIR HOUSING ACT |
| | REGULATIONS,24 CODE OF FEDERAL REGULAT- |
| | IONS (CFR) 100.205 (C) (3) (IV). |
| | REQUIRMENT#7 PARAGRAPH 2. DESIGNATE |
| | WHICH DESIGN SPECIFICATION IS BEING USED |
| | A OR B OF THE FAIR HOUSING ACT. |
| | SHOW DETAILS,AS ILLUSTRATED IN THE |
| | FAIR HOUSING ACT DESIGN MANUAL. |
| | END OF COMMENTS QUESTIONS CONTACT |
| | PAUL SCHMITZ 561-659-8096 X 8233 |