| Date |
Text |
| 2001-03-29 00:00:00 | ****************UNSAT **************** |
| | |
| | 1)NOTE:PLEASE NOTE WIRE SIZE SHOWN FOR |
| | "MCC" AT 500MCM AL. PLEASE SEE 75DEGREE |
| | COLLUMN IN 310-16. "310A"`S |
| | 2)NOTE: PLEASE NOTE THAT MANY PAGES ARE |
| | NOT READABLE. PRINT IS BLURRED AND VERY |
| | SMALL. MOSTLY ON SHEETS THAT GIVE YOU |
| | A COMPLETE OVER VIEW OF BLDG. |
| | |
| | 3)NOTE:E.2.2.2 MISSING OUTLETS PER LOCAL |
| | CODE. PLEASE NOTE THAT THE LOCAL CODE |
| | REQ`S MIN OUTLET SPACING OF EVERY 12` IN |
| | OFFICE SPACE AND EVERY 20`OF WALL SPACE |
| | IN STORAGE/HALLWAY AREAS. ONLY WALLS OF |
| | UNENCUMBERED SPACE. 210-50 |
| | |
| | 4)NOTE: PLEASE NOTE THAT THERE ARE SHEET |
| | S WITH NO ELECTRICAL SHOWN.E.2.2.2, |
| | E.4.1.2,E.4.1.3,E.4.2.0,E.4.2.2 ,,,,,, |
| | |
| | 5)NOTE: PLEASE NOTE ALL HOUSE LOADS THAT |
| | ARE CONTINUOUS NEED TO BE SHOWN AT 125% |
| | WHERE ARE LOADS SHOWN FOR "MCC". |
| | RISER DIAGRAM IS MISSING CONDUIT/WIRE |
| | SIZE FROM MCC MAIN TO MCC.? PLEASE CLARI |
| | FY. |
| | |
| | 6)NOTE: IN ADDITION; PLEASE SHOW CONDUIT |
| | AND WIRE SIZES ON LINE DIAGRAM FOR |
| | RISER. WE HAVE RUN INTO MANY PROBLEMS |
| | ON JOBS WHERE CONTRACTORS ARE NOT LOOKIN |
| | G AT PANEL SCHEDULES FOR CONDUIT AND WIR |
| | E SIZES. CONDUIT AND WIRE SIZES CAN BE S |
| | HOWN AS TYPICAL FOR COMMON UNITS. |
| | |
| | 7)NOTE: PLEASE CLARIFY GROUNDING ELECTRO |
| | DE SYSTEM.PER 250-50 |
| | |
| | 8)NOTE: PLEASE CLARIFY TYPE OF FUEL FOR |
| | GENERATOR. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS OR |
| | IF YOU WOULD LIKE A MEETING, PLEASE CALL |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |