| 2001-04-05 00:00:00 | 1 THIS BUILDING WILL BE IN AN FLOOD |
| | ZONE A5 WITH A 7.0' BFE |
| | 2THIS WILL BE A THRESHOLD BUILDING AND |
| | REQUIRES AN THRESHOLD INSPECTION PLAN |
| | AND INSPECTOR.CONTACT DON NEELY FOR |
| | ADDITIONAL INFORMATION659-8096 X 8333. |
| | 3PLEASE PROVIDE A RECNT PROPERTY |
| | SURVEY WITH THE PERMIT APPLICATION. |
| | 4SHOW HOW THE GLAZED PORTIONS OF THE |
| | BLDG WILL COMPLY WITH THE CITY'S |
| | HURRICANE MISSILE IMPACT ORDINANCE. |
| | 5IMPACT FEES MUST BE PAID TO THE |
| | COUNTY BEFORE A PERMIT CAN BE ISSUED. |
| | CALL 233-5025 FOR MORE INFORMATION. |
| | 6AT TIME OF PERMIT APPLICATION PROVIDE |
| | TEST DATA - PRODUCT APPROVALS FOR THE |
| | DOORS WINDOWS AND ROOF COVERING.SEE |
| | SBC 104.2. |
| | 7RESIDENTIAL UNIT TYPES A AND D HAVE |
| | TRAVEL DISTANCES > 75' AND MUST COMPLY |
| | WITH SBC 1004.1.4 AND SBC 1004.1.2. |
| | 8THE EXIT STAIR LAYOUT DOES NOT COMPLY |
| | WITH SBC 1004.1.4. |
| | 9SBC 412.6.2 REQUIRES AT LEAST ONE |
| | EXIT ACCESS WITHOUT TRAVEL THROUGH AN |
| | ELEVATOR LOBBY. |
| | 10THE EXIT DISCHARGE FOR THE NORTH |
| | HALF OF THE STAIRS DOES NOT COMPLY WITH |
| | SBC 1010. |
| | 11 PROVIDE COPIES OF THE SOIL AND WIND |
| | TUNNEL REPORTS. |
| | 12SPECIFY FIRE RETARDANT LUMBER ON |
| | SHEET A6 AND AS NECESSARY THROUGHOUT. |
| | 13SHEET S7 DOES NOT SHOW DESIGN LOADS |
| | FO CORRIDORS OR PUBLIC ROOMS AND THE |
| | LOBBIES ARE SHOWN AS 40 PSF.SEE SBC |
| | 1604.1. |
| | 14LATERAL SOIL PRESSURE IS NOT SHOWN |
| | IN THE DESIGN LOADS FOR THE GARAGE. |
| | SEE SBC 1608.1. |
| | 15SHOW THE DESIGN LOADS FOR THE |
| | VARIOUS RAILINGS.SEE SBC 1608.2 |
| | 16WATER PROOFING OR DAMP PROOFING |
| | MEASURES ARE NOT SHOWN FOR THE PORTIONS |
| | OF THE GARAGE BELOW GRADE.SBC 1814. |
| | 17SHOW THE LOCATION OF THE RELIEF |
| | VENTS IN THE STAIRS AND THE |
| | CALCULATIONS AND OPERATION TO MAINTAIN |
| | THE 2500CFM REQUIRED BY SBC 412.11 #5. |
| | OR COMPLY WITH SBC 1005.6. |
| | 18HOW WILL SMOKE CONTROL FOR THE |
| | WINDOWLESS ROOMS BE PROVIDED?SBC |
| | 412.5. |
| | 19SHOW THE VENTILATION FOR THE GARAGE. |
| | SBC 411.4.2. |
| | 20ELECTRICAL PANELS E17A AND E17B BOTH |
| | SHOW NORTH STAIRS FANS.THE MECHA |
| | PLANS SHOW 5 HP AND THE LEEC PLANS SHOW |
| | 10 HP FANS.PLEASE CLARIFY. |
| | 21SHOW THE EMERGENCY ROOF DRAIN |
| | OVERFLOW METHOD.SBC 1517.6.4.3. |