| Plan Review Notes For Permit 01030146 |
| Permit Number |
01030146 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-20 00:00:00 | PROVISO: | | | THIS INSTALLATION SHALL COMPLY WITH | | | NFPA 99C 1999 EDITION. | | | | | | PIPE SHALL BE PROMINENTLY LABELED PRIOR | | | TO INSTALLATION PER 4-3.2.2.2 | | | | | | PRESSURE TEST PER 4-3.4.1.1 SHALL BE | | | PRIOR TO WALLS BEING CLOSED. | | | | | | ALARM PANELS SHALL BE POWERED BY LIFE | | | SAFETY BRANCH OF THE EMERGENCY SYSTEM | | | PER 4-3.1.2.7 | | | | | | PIPE MATERIAL TO BE PER 4-3.1.2.7 (C) | | | | | | PIPING SHOWN AS MEDICAL EVACUATION ON | | | THIS PLAN IS TO BE INSTALLED PER 4-3.3 | | | WASTE ANESTHETIC GAS DISPOSAL SYSTEMS | | | OR SUBMIT REVISION DEFINING USE OF THIS | | | SYSTEM FOR REVIEW. | | | | | | CALL FOR INSPECTION PRIOR TO CONCEALING | | | WORK. CALL FOR REQUIRED INSPECTIONS AND | | | ACCEPTANCE TESTS REQUIRED BY THIS | | | OFFICE. | | | CALL PAUL SCHMITZ @ (561) 659-8096 EXT | | | 8233 OR JOHN LEECH EXT 8369 IF YOU HAVE | | | ANY QUESTIONS ON REQUIRED TESTS OR | | | INSPECTIONS. |
|