2001-04-17 00:00:00************* REVISION NEEDED **********
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE SUBMIT AIC RATINGS FOR ALL BEFORE
 FINAL INSPECTION.
  
 REVISE ANY OTHER CHANGES ON SAME PLANS
 BEFORE FINAL ALSO.(AS-BUILTS)
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  