| 2001-04-12 00:00:00 | CHECKLIST: |
| | 1-PROVIDE PROFESSIONAL SURVEY SHOWING |
| | BUILDING LAYOUT AS REQUESTED ON |
| | CHECKLIST DATED 3-27-01. |
| | -NOTE: SKETCH THAT WAS SUBMITTED AND |
| | APPROVED BY ZONING WAS NOT SUBMITTED |
| | WITH THIS PACKAGE. PLEASE RESUBMIT. |
| | 2-UNABLE TO CHECK TABLE 600 OF SBC 1997 |
| | BECAUSE THERE IS NOT SURVEY OR SITE |
| | PLAN SHOWING BUILDING LOCATION IN |
| | REFERENCE TO THE PROPERTY LINES. |
| | 3-PROVIDE PRODUCT APPROVAL FOR: |
| | -ENTRY DOORS WITH TRANSOM ABOVE AS A |
| | SINGLE ASSEMBLY AS SHOWN ON PLANS. |
| | OR ENGINEER OF RECORD TO PROVIDE |
| | SECTION THRU ENTRY DOORS AREA SHOWING |
| | LINTEL SPECIFICATIONS. THEN, PROVIDE |
| | PRODUCT APPROVAL FOR ENTRY DOORS AND |
| | ARCHED WINDOW SEPARATELY. |
| | -SINGLE HUNG WINDOWS PRODUCT APPROVAL |
| | WAS ORIGINALLY SUBMITTED WITH DRAWINGS |
| | THAT WERE NOT LEGIBLE. NOW, NO PRODUCT |
| | APPROVAL WAS SUBMITTED. |
| | -SLIDING GLASS DOORS WITH TRANSOM ABOVE |
| | SINGLE ASSEMBLY AS SHOWING ON PLANS. |
| | OR, ENGINEER OF RECORD TO SHOW WALL |
| | SECTION SPECIFYING STRUCTURAL LINTEL. |
| | THEN, PROVIDE PRODUCT APPROVAL FOR |
| | DOORS AND FIXED WINDOW SEPARATELY. |
| | -HALF ROUND WINDOWS. |
| | -WINDOW MULLIONS. |
| | -GARAGE DOORS THAT MEET THE DESIGN |
| | PRESSURES CALCULATED BY THE ENGINEER |
| | OF RECORD (37PSF). |
| | 4-TYPICAL WALL SECTION SHOWS TIE BEAM |
| | TO BE AT 10'-0". CLARIFY IF THERE ARE |
| | NOT LINTELS, THEN WHAT IS IN BETWEEN |
| | THE WINDOWS AND THE TIE BEAM. REMEMBER |
| | THAT TIE BEAM IS 8"X12". |
| | PROVIDE SECTIONS WITH DIMENSIONS |
| | SHOWING LOCATION OF DOORS AND WINDOWS |
| | HEADS. |
| | 5-PROVIDE COMPLETE SPECIFICATIONS FOR |
| | CEILING INSTALLATION AT ENTRY AND REAR |
| | PORCH. AS REQUIRED BY SECTION 2504.2 |
| | SBC/97. CLEARLY SPECIFY ALL MATERIALS |
| | AND FASTENERS TO BE USED. SEE ASTM |
| | C926 AND ASTM C1063. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 659-8096 EXT. 8232. |