| Plan Review Notes For Permit 01030121 |
| Permit Number |
01030121 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-04-12 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE FIRST NOTE | | | FROM PREVIOUS REVIEW WAS NOT SUBMITTED. | | | PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | THIS IMFORMATION IS VERY IMPORTANT AND | | | IS NOT SOMETHING THAT I CAN REDLINE ON | | | PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS , | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|