| 2001-03-10 00:00:00 | DENIED; | | | | | | 1.DRYER VENT REQUIRED. | | | | | | 2.BATHROOM WINDOWS SHALL HAVE A CLEAR | | | OPEN AREA OF 3 SQ. FT. OR EXHAUST FANS | | | ARE REQUIRED.SMC 503.3.1. | | | | | | 3.EQUIPMENT IS TO SMALL. 5 TON IS | | | REQUIRED NOT 3 TON. | | | | | | 4.ENERGY CAULKS SHOW A SEER VALUE OF | | | 13.5 A/C PLAN SHOWS 12. CHANGE ENERGY | | | CAULKS OR EQUIPMENT. | | | | | | 5.RETURN AIR IS REQUIRED FROM MASTER | | | BEDROOM SUITE. | | | | | | A/C PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|