| 2001-03-12 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 4) NOTE: PLEASE SHOW GROUNDING |
| | ELECTRODEGOING TO BUILDING STEEL AND |
| | COLD WATER |
| | PER 250-50. |
| | |
| | 5) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | 6) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | |
| | 7)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | GARAGE PER 210-52 G AND TO BE GFI PER |
| | 210-8. |
| | |
| | 8)NOTE: PLEASE NOTE PER F.A.C 61G15-23. |
| | 002 AND 471.025 ALL CHANGES ON PLANS |
| | NEED TO SIGNED AND DATED BY THE |
| | ENGINEEROF RECORD. PLEASE MAKE ALL |
| | CHANGES IN |
| | PRINTED INK OR SIGN AND DATE EACH |
| | CHANGE. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |