Plan Review Notes
Plan Review Notes For Permit 01030121
Permit Number 01030121
Review Stop E
Sequence Number 1
Notes
Date Text
2001-03-12 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50.
  
 5) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 6) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 7)NOTE: PLEASE NOTE MISSING OUTLET FOR
 GARAGE PER 210-52 G AND TO BE GFI PER
 210-8.
  
 8)NOTE: PLEASE NOTE PER F.A.C 61G15-23.
 002 AND 471.025 ALL CHANGES ON PLANS
 NEED TO SIGNED AND DATED BY THE
 ENGINEEROF RECORD. PLEASE MAKE ALL
 CHANGES IN
 PRINTED INK OR SIGN AND DATE EACH
 CHANGE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372