| Plan Review Notes For Permit 01030086 |
| Permit Number |
01030086 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-05 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE | | | TO BE A MINIMUM OF THREE FEET FROM | | | AIR CONDITONER DIFFUSERS. | | | 2) HOOD EXTINGUISHING SYSTEMS ARE TO | | | BE TIED INTO FIRE ALARM SYSTEM. | | | 3) FIRE ALARM SYSTEM TO BE MONITORED BY | | | A LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | 4) AFTER INSTALLATION, SYSTEM TO BE | | | TESTED WITH FIRE RESCUE PERSONNEL. | | | 5) SYSTEM TO BE CLASS A OR FULLY | | | ADDRESSABLE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|