| Notes |
| Date |
Text |
| 2001-05-22 00:00:00 | REVIEW NOTES..DENIED.. | | | | | | 1) 2 HDCP TOILET ROOMS, 1 MALE AND 1 | | | FEMALE ARE REQUIRED. | | | | | | 2) MANUFACTURE'S SPEC. SHEET FOR HUMIDI | | | FIER REQUIRED. ALSO BACKFLOW IS NOT RE- | | | QUIRED FOR HUMIDIFIER, A WATTS N36 VAC- | | | UMN BREAKER OR EQUIVALNT WILL WORK. | | | | | | 3) FRENCH DRAINS ARE NOT APPROVED. | | | DRYWELL'S ARE ACCEPTABLE. | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|