Plan Review Notes For Permit 01030082
Permit Number 01030082
Review Stop P
Sequence Number 2
Notes
Date Text
2001-05-22 00:00:00REVIEW NOTES..DENIED..
  
 1) 2 HDCP TOILET ROOMS, 1 MALE AND 1
 FEMALE ARE REQUIRED.
  
 2) MANUFACTURE'S SPEC. SHEET FOR HUMIDI
 FIER REQUIRED. ALSO BACKFLOW IS NOT RE-
 QUIRED FOR HUMIDIFIER, A WATTS N36 VAC-
 UMN BREAKER OR EQUIVALNT WILL WORK.
  
 3) FRENCH DRAINS ARE NOT APPROVED.
 DRYWELL'S ARE ACCEPTABLE.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377