Plan Review Notes
Plan Review Notes For Permit 01030082
Permit Number 01030082
Review Stop M
Sequence Number 2
Notes
Date Text
2001-06-05 00:00:00********************DENIED**************
  
 PLEASE CLARIFY DESCREPANCY BETWEEN
 DRAWING M2.1, 1 1/2" CONDENSATE DRAIN
 DOWN FROM ROOF TO FLOOR DRAIN AND M2.2
 - DETAIL 01, CONDENSATE FRENCH DRAIN.
  
 ROOF CONDENSATE IS NOT GOING TO FLOOR
 DRAIN...CORRECT?
  
 NOTE:AS PER AMENDED 1994 SPC 804.3,
 CONDENSATE FOR UNITS LARGER THAN
 3 TONS MAY TERMINATE IN A DRYWELL
 NOT A FRENCH DRAIN.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.