Plan Review Notes
Plan Review Notes For Permit 01030082
Permit Number 01030082
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-05-15 00:00:001) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED PRIOR TO
 RECEIVING ANY FINAL APPROVALS. PLEASE
 PROVIDE SEPARATE PLANS AND PERMITS FOR
 FIRE SPRINKLER INSTALLATIONS.
 2) PLEASE SUBMIT SEPARATE PLANS AND
 PERMITS FOR THE FIRE ALARM SYSTEM
 INSTALLATION. SMOKE DETECTORS WHEN
 INSTALLED ARE TO BE A MINIMUM OF THREE
 FEET FROM AIR CONDITIONER DIFFUSERS.
 BOTH THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEMS ARE TO BE SUPERVISED BY
 A UL LISTED CENTRAL STATION APPROVED
 BY THE FIRE RESCUE DEPARTMENT.
 3) THE FUTURE EXPANSION AREA IS TO HAVE
 EMERGENCY LIGHTING FIXTURES INSTALLED AS
 A BASE OR SHELL BUILDING WOULD HAVE. THE
 MINIMUM REQUIREMENTS FOR OCCUPANCY SHALL
 BE MET WITH ADDITIONAL WORK OR OCCUPANCY
 BY SEPARATE PERMIT.
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FUEL INSTALLATION.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910