| Plan Review Notes For Permit 01030082 |
| Permit Number |
01030082 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-05-15 00:00:00 | 1) ENTIRE BUILDING IS TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED PRIOR TO | | | RECEIVING ANY FINAL APPROVALS. PLEASE | | | PROVIDE SEPARATE PLANS AND PERMITS FOR | | | FIRE SPRINKLER INSTALLATIONS. | | | 2) PLEASE SUBMIT SEPARATE PLANS AND | | | PERMITS FOR THE FIRE ALARM SYSTEM | | | INSTALLATION. SMOKE DETECTORS WHEN | | | INSTALLED ARE TO BE A MINIMUM OF THREE | | | FEET FROM AIR CONDITIONER DIFFUSERS. | | | BOTH THE FIRE SPRINKLER SYSTEM AND FIRE | | | ALARM SYSTEMS ARE TO BE SUPERVISED BY | | | A UL LISTED CENTRAL STATION APPROVED | | | BY THE FIRE RESCUE DEPARTMENT. | | | 3) THE FUTURE EXPANSION AREA IS TO HAVE | | | EMERGENCY LIGHTING FIXTURES INSTALLED AS | | | A BASE OR SHELL BUILDING WOULD HAVE. THE | | | MINIMUM REQUIREMENTS FOR OCCUPANCY SHALL | | | BE MET WITH ADDITIONAL WORK OR OCCUPANCY | | | BY SEPARATE PERMIT. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY FUEL INSTALLATION. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|