| Plan Review Notes For Permit 01030082 |
| Permit Number |
01030082 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-06-12 00:00:00 | 1- OUTLET SPACING DOES NOT MEET LOCAL | | | CODE,IN OFFICE AREAS IT IS EVERY | | | 12' AND IN ALL OTHER ARES IT IS EVERY | | | 20'.ONLY WHAREHOUSE USED FOR | | | STORAGE ARE EXEMPT!!!!!!!!!! 210-50 | | | | | | 2-VALUE FOR THE ELECTRICAL WORK WILL | | | HAVE TO INCLUDE ALL EQUIPMENT AND | | | LABOR!!PER 104.7.5 | | | 3-AIC RATINGS FOR MAINS IS SHOWN BUT | | | NONE FOR THE PANELS AND CIRCUIT | | | BREAKERS!ON THE PANEL SCHEDULE PLEASE | | | LIST THE AIAIC RATING FOR ALL THE | | | CIRCUIT BREAKERS IN THE PANEL!!!!!IF | | | NOT MOST WILL HAVE TO BE 65,000 BASED | | | ON WHAT IS SHOWN ON DRAWINGS |
|