1 |
|
| Notes |
| Date |
Text |
| 2001-03-20 00:00:00 | DENIED; | | | | | | 1.SUBMIT OCCUPANT LOAD PER TABLE 407 OF | | | THE 94 SPC. SEE SEC. 407.1.3 FOR | | | ALLOWABLE DEDUCTIBLE AREAS. COMPLY | | | WITH TABLE 407 FOR MIN. FIXTURES | | | REQUIRED. | | | | | | 2.WATER HEATER TO BE READILY ACCESSIBLE. | | | SOULD BE MOUNTED ON FLOOR. | | | | | | 3.REPLACE HUB DRAIN WITH FLOOR SINK. | | | | | | 4.ROOM 118 FD-1 IS UNVENTED. | | | | | | 5.FUTURE 4" WASTE PIPE SHALL COMPLY WITH | | | 714.3. NO DEAD ENDS. | | | | | | 6.FLOOR DRAIN IN JANITORS ROOM SHALL | | | HAVE A TRAP PRIMER. | | | | | | 7.DRINKING FOUNTAIN NOT SHOWN ON FLOOR | | | PLAN OR ON RISER DIAGRAM.DRINKING | | | FOUNTAIN TO COMPLY WITH FACBC 4.1.3 | | | (10) AND 4.13. | | | | | | 8.SHEET M-3 (HUMIDIFIER) DISCHARGE OF | | | WASTE WATER OVER 140 DEG. IS NOT | | | PERMITED.807.3 | | | | | | 9.SHEET M-2.2 CONDENSATE FROM A/C UNITS | | | TO BE PIPED TO STORM DRAINAGE NOT | | | SANITARY. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|