2001-03-22 00:00:00*****************DENIED*****************
  
 CONDENSATE FROM ROOFTOP UNITS SHALL NOT
 EMPTY INTO SANITARY DRAIN AS PER
 AMENDED 1994 SPC 804.3.
  
 AS PER 1997 SMC 406.1, UNITS WITH FAN
 CAPACITY GREATER THAN 2,000 CFM SHALL
 HAVE FAN SHUT DOWN BY DUCT SMOKE
 DETECTOR WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS
 (NFPA 90A 4-4.4.3)
  
 NO COMBUSTIBLES ABOVE CEILING IN RETURN
 AIR PLENUM - 1997 SMC 609.1.1.
  
 SEPARATE PERMIT AND PLANS REQUIRED FOR
 UNDERGROUND FUEL OIL TANK.