| Date |
Text |
| 2001-03-08 00:00:00 | 1) PLEASE BE ADVISED THAT THIS SITE |
| | MAY BE IN THE CITY FIRE LIMITS. CERTAIN |
| | RESTRICTIONS APPLY IN THE FIRE LIMITS |
| | TO THE INSTALLATION OF ABOVEGROUND FUEL |
| | TANKS AND FLAMMABLE LIQUID TANKS. |
| | SEPARATE PLANS AND PERMITS REQUIRED |
| | PRIOR TO THE INSTALLATION OF ANY |
| | FUEL TANKS. |
| | 2) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR THE FIRE SPRINKLER SYSTEM RENOVATION |
| | AND REMODEL. |
| | 3) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR THE INSTALLATION OF THE FIRE ALARM |
| | SYSTEM. CUT SHEETS, WIRING DIAGRAM, AND |
| | BATTERY CALCULATIONS ARE TO BE PROVIDED. |
| | 4) KNOX-BOX RAPID ENTRY SYSTEMS ARE TO |
| | BE PROVIDED FOR FIRE RESCUE ACCESS. |
| | 5) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR GATES AND ELECTRICAL SYSTEMS. |
| | OPENINGS AT GATE LOCATIONS MUST BE |
| | TWENTY FEET IN CLEAR WIDTH. HOW IS |
| | ACCESS ACHIEVED THRU THE SLIDING GATE |
| | IF LOSS OF POWER SHOULD OCCUR. |
| | 6) DUCT SMOKE DETECTORS REQUIRED IN ALL |
| | AHU SYSTEMS OVER 2000 CFM. WHEN |
| | ACTIVATED, THESE SYSTEMS MUST SHUT DOWN |
| | AIR HANDLING EQUIPMENT AND ACTIVATE THE |
| | FIRE ALARM SYSTEM. |
| | 7) NO INTERIOR FINISH CLASSIFICATION |
| | INFORMATION PROVIDED WITH PLANS. |
| | 8) BUILDING ADDRESS REQUIRED PER CITY |
| | CODE REQUIREMENTS. |
| | 9) NO EMERGENCY LIGHTING SHOWN IN |
| | EXPANSION AREA. WHAT WILL THIS AREA BE |
| | USED FOR AND WHEN. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |