Plan Review Notes
Plan Review Notes For Permit 01030082
Permit Number 01030082
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-03-08 00:00:001) PLEASE BE ADVISED THAT THIS SITE
 MAY BE IN THE CITY FIRE LIMITS. CERTAIN
 RESTRICTIONS APPLY IN THE FIRE LIMITS
 TO THE INSTALLATION OF ABOVEGROUND FUEL
 TANKS AND FLAMMABLE LIQUID TANKS.
 SEPARATE PLANS AND PERMITS REQUIRED
 PRIOR TO THE INSTALLATION OF ANY
 FUEL TANKS.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE SPRINKLER SYSTEM RENOVATION
 AND REMODEL.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF THE FIRE ALARM
 SYSTEM. CUT SHEETS, WIRING DIAGRAM, AND
 BATTERY CALCULATIONS ARE TO BE PROVIDED.
 4) KNOX-BOX RAPID ENTRY SYSTEMS ARE TO
 BE PROVIDED FOR FIRE RESCUE ACCESS.
 5) SEPARATE PLANS AND PERMITS REQUIRED
 FOR GATES AND ELECTRICAL SYSTEMS.
 OPENINGS AT GATE LOCATIONS MUST BE
 TWENTY FEET IN CLEAR WIDTH. HOW IS
 ACCESS ACHIEVED THRU THE SLIDING GATE
 IF LOSS OF POWER SHOULD OCCUR.
 6) DUCT SMOKE DETECTORS REQUIRED IN ALL
 AHU SYSTEMS OVER 2000 CFM. WHEN
 ACTIVATED, THESE SYSTEMS MUST SHUT DOWN
 AIR HANDLING EQUIPMENT AND ACTIVATE THE
 FIRE ALARM SYSTEM.
 7) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED WITH PLANS.
 8) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 9) NO EMERGENCY LIGHTING SHOWN IN
 EXPANSION AREA. WHAT WILL THIS AREA BE
 USED FOR AND WHEN.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910