| Date |
Text |
| 2001-03-27 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE:PLEASE NOTE THAT UNDER |
| | COUNTYWIDE ADMINISTRATIVE AND CITY CODE. |
| | VALUE OF WORK BEING PERFORMED IS TO |
| | INCLUDE LABOR AND MATERIALS. THIS VALUE |
| | IS |
| | ALSO TO INCLUDE ALL ELECTRICAL |
| | EQUIPMENTTHAT MAY BE SUPPLIED BY THE |
| | OWNER. |
| | PLEASE NOTE THAT THE NOTE ON PLANS |
| | PERTAINING TO "OWNER FURNISHED" |
| | /"CONTRACTOR RECEIVED AND |
| | INSTALLED". ALL ELECTRICAL EQUIPMENT |
| | NEEDS TO BE SHOWN IN VALUE OF |
| | APPLICATION. THIS IS TO INCLUDE |
| | GENERATOR AND ATS ETC. IF THERE ARE ANY |
| | QUESTIONS ON ANY OF THE ABOVE PLEASE |
| | CALL. |
| | |
| | 2)NOTE: PLEASE PROVIDE CLARIFICATION ON |
| | THE GFI PROTECTION OF MAIN SERVICE PER |
| | 230-95. |
| | |
| | 3)NOTE: PLEASE NOTE A MEANS OF |
| | DISCONNECT REQ`D FOR POWER COMING IN |
| | FROM GENERATOR. 225-31. PLEASE NOTE |
| | THAT THE DISCONNECT NEEDS TO BE GROUPED |
| | PER 230-72. |
| | THE REQ`MENST FOR THIS DISCONNECT NEEDS |
| | TO MEET 230-76 AND 230-79. |
| | |
| | 4)NOTE: PLEASE NOTE THAT COLOR CODING |
| | FOR 277/480 FEEDERS "B","P","Y". GRAY. |
| | |
| | |
| | PLEASE ADDRESS AND SUBMIT THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE |
| | ANY QUESTIONS, PLEASE CALL. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRCIAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |