2001-03-27 00:00:00**************** UNSAT *****************
  
 1)NOTE:PLEASE NOTE THAT UNDER
 COUNTYWIDE ADMINISTRATIVE AND CITY CODE.
 VALUE OF WORK BEING PERFORMED IS TO
 INCLUDE LABOR AND MATERIALS. THIS VALUE
 IS
 ALSO TO INCLUDE ALL ELECTRICAL
 EQUIPMENTTHAT MAY BE SUPPLIED BY THE
 OWNER.
 PLEASE NOTE THAT THE NOTE ON PLANS
 PERTAINING TO "OWNER FURNISHED"
 /"CONTRACTOR RECEIVED AND
 INSTALLED". ALL ELECTRICAL EQUIPMENT
 NEEDS TO BE SHOWN IN VALUE OF
 APPLICATION. THIS IS TO INCLUDE
 GENERATOR AND ATS ETC. IF THERE ARE ANY
 QUESTIONS ON ANY OF THE ABOVE PLEASE
 CALL.
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION ON
 THE GFI PROTECTION OF MAIN SERVICE PER
 230-95.
  
 3)NOTE: PLEASE NOTE A MEANS OF
 DISCONNECT REQ`D FOR POWER COMING IN
 FROM GENERATOR. 225-31. PLEASE NOTE
 THAT THE DISCONNECT NEEDS TO BE GROUPED
 PER 230-72.
 THE REQ`MENST FOR THIS DISCONNECT NEEDS
 TO MEET 230-76 AND 230-79.
  
 4)NOTE: PLEASE NOTE THAT COLOR CODING
 FOR 277/480 FEEDERS "B","P","Y". GRAY.
  
  
 PLEASE ADDRESS AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372