Plan Review Notes
Plan Review Notes For Permit 01030082
Permit Number 01030082
Review Stop B
Sequence Number 1
Notes
Date Text
2001-03-13 00:00:00PROJECT# 01030082
 531 SOUTHERN BLVD.
 BURR COMPUTER ENVIROMENTS
 (781) 374-8644
  
 THE CODE COMMENTS LISTED BELOW ARE FROM
 THE 1997 STANDARD BUILDING CODE.
  
 1)- SBC 407.1.3.1: FIRE SPRINKLER PLANS
 ARE TO BE PART OF THE PERMIT APPLICATION
 PACKAGE BEFORE THE BUILDING PERMIT CAN
 BE ISSUED.
  
 2)- SBC 104.2.2: ADDITIONAL INFORMATION
 REQUIRED: IS THERE AREAS OF THE BUILDING
 THAT CONTAIN LARGE QUANITITIES OF
 PRINTED CIRCUIT BOARDS USED FOR SWITCHES
 IN THE TELECOMMUNICATION PROCESS?
  
 3)- SBC 308.2.1: H-4 HEALTH HAZARDS-
 TOXIC SOLIDS, LIQUIDS,CORROSIVES,IRRI-
 TANTS, SENSITIZERS IN EXCESS OF AMOUNTS
 GIVEN IN TABLE 308.2D.
 IN SPRINKLERED BUILDINGS, NOT IN A CABI-
 NET CORROSIVES, IRRITANTS
 SOLIDS : 10,000LBS.
 LIQUIDS:1,000GAL.
 GASSES :1,300 CU FT.
  
 PLAN : S-1 DEPICTS 6,700 LBS./ RACK.
 PLAN : FP.2 DEPICTS 3 RACKS X 6,700 LBS=
 20,100 LBS.IN EXCESS OF 10,000LBS.
 IN TABLE 308.2D = H4 HAZARDOUS OCCUPANCY
 FOR ROOM 114 DC POWER ROOM.
  
 4)- SBC308.2.3: HAZARDOUS OCCUPANCY
 SEPERATION REQUIREMENTS BETWEEN BUSINESS
 FACTORY VS. H-4 OCCUPANCY.
 WALLS: 1 HRS.
 OPENING PROTECTIVES : 3/4 HR OPEN PRO
  
 5)- SBC 407.2.1 STORAGE & DISPENSING
 AREAS: IN EXCESS OFTHE EXEMPT AMOUNTS
 SPECIFIED IN TABLE 308.2D.
 407.2.2EXPLOSION VENTING OR EXPLOSION
 SUPPERSSION 1-7.
 407.2.3.2 SPILL CONTROL.
 407.2.4.2 EXHAUST VENTILATION 1-4.
 407.2.5.1 EMERGENCY ALARM & DETECTION.
 407.2.6.2 LIQUID TIGHT FLOORS.
 407.2.9.1 ELEC WIRING EQUIPMENT INSTALL
 ED IN ACCORDANCE WITH NFPA 70.
 407.2.9.4 STANDBY POWER SHALL BE CONNECT
 ED TO THE FOLLOWING: MECHANICAL VENTIL-
 ATION SYSTEM, ALARM SYSTEM,
 DETECTION SYSTEM AND THE EMER-
 GENCY ILLUMINATION IN ACCORDANCE
 WITH 1016.2.
 407.2.10 IDENIFICATION: VISIBLE HAZARD
 IDENIFICATION SIGNS AS SPECIFIED
 IN NFPA 704.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412.