| 2001-03-13 00:00:00 | PROJECT# 01030082 |
| | 531 SOUTHERN BLVD. |
| | BURR COMPUTER ENVIROMENTS |
| | (781) 374-8644 |
| | |
| | THE CODE COMMENTS LISTED BELOW ARE FROM |
| | THE 1997 STANDARD BUILDING CODE. |
| | |
| | 1)- SBC 407.1.3.1: FIRE SPRINKLER PLANS |
| | ARE TO BE PART OF THE PERMIT APPLICATION |
| | PACKAGE BEFORE THE BUILDING PERMIT CAN |
| | BE ISSUED. |
| | |
| | 2)- SBC 104.2.2: ADDITIONAL INFORMATION |
| | REQUIRED: IS THERE AREAS OF THE BUILDING |
| | THAT CONTAIN LARGE QUANITITIES OF |
| | PRINTED CIRCUIT BOARDS USED FOR SWITCHES |
| | IN THE TELECOMMUNICATION PROCESS? |
| | |
| | 3)- SBC 308.2.1: H-4 HEALTH HAZARDS- |
| | TOXIC SOLIDS, LIQUIDS,CORROSIVES,IRRI- |
| | TANTS, SENSITIZERS IN EXCESS OF AMOUNTS |
| | GIVEN IN TABLE 308.2D. |
| | IN SPRINKLERED BUILDINGS, NOT IN A CABI- |
| | NET CORROSIVES, IRRITANTS |
| | SOLIDS : 10,000LBS. |
| | LIQUIDS:1,000GAL. |
| | GASSES :1,300 CU FT. |
| | |
| | PLAN : S-1 DEPICTS 6,700 LBS./ RACK. |
| | PLAN : FP.2 DEPICTS 3 RACKS X 6,700 LBS= |
| | 20,100 LBS.IN EXCESS OF 10,000LBS. |
| | IN TABLE 308.2D = H4 HAZARDOUS OCCUPANCY |
| | FOR ROOM 114 DC POWER ROOM. |
| | |
| | 4)- SBC308.2.3: HAZARDOUS OCCUPANCY |
| | SEPERATION REQUIREMENTS BETWEEN BUSINESS |
| | FACTORY VS. H-4 OCCUPANCY. |
| | WALLS: 1 HRS. |
| | OPENING PROTECTIVES : 3/4 HR OPEN PRO |
| | |
| | 5)- SBC 407.2.1 STORAGE & DISPENSING |
| | AREAS: IN EXCESS OFTHE EXEMPT AMOUNTS |
| | SPECIFIED IN TABLE 308.2D. |
| | 407.2.2EXPLOSION VENTING OR EXPLOSION |
| | SUPPERSSION 1-7. |
| | 407.2.3.2 SPILL CONTROL. |
| | 407.2.4.2 EXHAUST VENTILATION 1-4. |
| | 407.2.5.1 EMERGENCY ALARM & DETECTION. |
| | 407.2.6.2 LIQUID TIGHT FLOORS. |
| | 407.2.9.1 ELEC WIRING EQUIPMENT INSTALL |
| | ED IN ACCORDANCE WITH NFPA 70. |
| | 407.2.9.4 STANDBY POWER SHALL BE CONNECT |
| | ED TO THE FOLLOWING: MECHANICAL VENTIL- |
| | ATION SYSTEM, ALARM SYSTEM, |
| | DETECTION SYSTEM AND THE EMER- |
| | GENCY ILLUMINATION IN ACCORDANCE |
| | WITH 1016.2. |
| | 407.2.10 IDENIFICATION: VISIBLE HAZARD |
| | IDENIFICATION SIGNS AS SPECIFIED |
| | IN NFPA 704. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412. |