| 2001-07-28 00:00:00 | REVISION UNSAT |
| | |
| | 1) PROVIDE DETAILED WALL SECTION OF |
| | EXTERIOR STUDIO WALL AT NEW OPENING FOR |
| | GLASS BLOCK. INDICATE WALL MATERIAL, |
| | FRAMING MATERIAL, HEADER SIZE AND |
| | MATERIAL, STRAPPING DETAILS, INTERIOR |
| | AND EXTERIOR FINISHES,ETC. |
| | |
| | 2) INDICATE TYPES OF MATERIALS THAT WILL |
| | BE USED TO ENCLOSE STUDIO WINDOW. |
| | |
| | 3) PLANS SUBMITTED FOR REVISION MUST BE |
| | SIGNED, SEALED AND DATED BY THE DESIGNER |
| | OF RECORD (ENGINEER). ENGINEER'S BLOCK |
| | STAMP IS REQUIRED ON PLANS. |
| | |
| | PRODUCT APPROVALS |
| | |
| | 1) PRODUCT APPROVALS SUBMITTED FOR DOORS |
| | DO NOT CORRESPOND TO THE DOUBLE FRENCH |
| | DOORS SHOWN ON THE PLANS. TWO (2) COPIES |
| | ARE REQUIRED. |
| | |
| | 2) PARTS OF THE PRODUCT APPROVAL |
| | SUBMITTED FOR THE GLASS BLOCK ARE |
| | ILLEGIBLE. PLEASE SUBMIT TWO (2) CLEAR, |
| | READABLE COPIES. |
| | |
| | 3)PROVIDE (2) CURRENT PRODUCT APPROVALS, |
| | KEY PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. |
| | PLYWOOD HURRICANE PANELS ARE ACCEPTIBLE |
| | IF DESIGNED IN ACCORDANCE WITH AMERICAN |
| | PLYWOOD ASSOCIATION GUIDELINES. YOU CAN |
| | NOT USE CUSTOM BUILT CEDAR SHUTTERS, |
| | UNLESS THEY COMPLY WITH THE CITY OF |
| | WEST PALM BEACH REQUIREMENTS FOR MISSLE |
| | IMPACT PROTECTION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |