| Plan Review Notes For Permit 01030051 |
| Permit Number |
01030051 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-29 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY LOCATION OF | | | SERVICE OR IS SERVICE EXISTING FROM | | | MAIN HOUSE? PLEASECLARFIY LOCATION OF | | | SERVICE. | | | PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2) NOTE: PLEASE SHOW GROUNDING | | | ELECTRODEGOING TO BUILDING STEEL AND | | | COLD WATER | | | PER 250-50. | | | | | | 3)NOTE: PLEASE NOTE BATH OUTLET REQ`D BY | | | 210-52 AND 210-11-C-3. | | | | | | 4) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | ONE WILL BE REQ`D FOR THIS ROOM. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANYQUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|