Plan Review Notes
Plan Review Notes For Permit 01030051
Permit Number 01030051
Review Stop E
Sequence Number 1
Notes
Date Text
2001-03-29 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY LOCATION OF
 SERVICE OR IS SERVICE EXISTING FROM
 MAIN HOUSE? PLEASECLARFIY LOCATION OF
 SERVICE.
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50.
  
 3)NOTE: PLEASE NOTE BATH OUTLET REQ`D BY
 210-52 AND 210-11-C-3.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 ONE WILL BE REQ`D FOR THIS ROOM.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved