| 2001-03-29 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - GLASS BLOCK |
| | - GLAZED DOUBLE ENTRY DOORS (INFORMATION |
| | THAT WAS SUBMITTED IS NOT ACCEPTABLE) |
| | |
| | 4) PROVIDE ATTIC VENTILATION PER 97 SBC |
| | SEC. 2309.7. |
| | |
| | 5) PROVIDE CRAWL SPACE VENTILATION PER |
| | 97 SBC SEC.1804.6.2.1. |
| | |
| | 6) SHEET 2 OF PLANS CONTAINS CONFLICTING |
| | INFORMATION AND IMPROPER DESIGN CRITERIA |
| | THE ACCEPTED DESIGN CRITERIA IS ASCE7-95 |
| | OR SEC. 1606 OF THE 1997 SBC. |
| | |
| | 7) PROVIDE DETAIL OF 2X8 RAFTER ATTACH- |
| | MENT TO EXISTING STRUCTURE. |
| | |
| | 8) PROVIDE ENERGY CALCULATIONS FOR NEW |
| | ADDITION AS REQUIRED BY THE 97 FLORIDA |
| | ENERGY CODE. |
| | |
| | 9) INDICATE INSULATION FOR WALLS, FLOORS |
| | AND CEILING OF ADDITION THAT COMPLIES |
| | WITH THE 97 FLORIDA ENERGY CODE. |
| | |
| | 10) PROVIDE STRUCTURAL DETAILS AND WALL |
| | SECTION OF EXISTING GUEST HOUSE WHERE |
| | OPENINGS WILL BE MADE TO ACCOMADATE NEW |
| | DOUBLE DOORS. |
| | |
| | 11)PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |