| Plan Review Notes For Permit 01030013 |
| Permit Number |
01030013 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-04-03 00:00:00 | DENIED | | | | | | 1) SITE SPECIFIC ENGINEERING MAKES | | | REFERENCE TO CURRENT SBCCI BUILDING CODE | | | THIS IS NOT ACCEPTABLE. THE PRODUCT MUST | | | CONFORM TO THE 1997 STANDARD BUILDING | | | CODE OR THE 1999 SOUTH FLORIDA BUILDING | | | CODE (LISTED ON THE FORM). PLEASE | | | CORRECT. | | | | | | 2) THE DESIGN PROFESSIONAL OF RECORD | | | THAT SIGNED AND SEALED THE PRODUCT | | | APPROVAL (SITE SPECIFIC) DID NOT SIGN | | | AND SEAL THE PLANS, WHICH ARE SIGNED AND | | | SEALED BY AN INTERIOR DESIGNER. AN | | | EXTERIOR DOOR IS NOT WITHIN THE SCOPE OF | | | AN INTERIOR DESIGNER AND REQUIRES | | | WINDLOAD CERTIFICATION BY AN ARCHITECT | | | OR ENGINEER. PLEASE HAVE PLANS SIGNED, | | | SEALED AND DATED BY APPROPRIATE DESIGN | | | PROFESSIONAL WITH TITLE BLOCK. | | | | | | 3) PRODUCT APPROVAL FOR DOORS INDICATES | | | NO IMPACT RESISTIBILITY. STORM PANELS OR | | | SMALL MISSLE IMPACT RESISTANT GLASS IS | | | REQUIRED AT 30 FT. OR MORE ABOVE GRADE. | | | PLEASE CLARIFY HOW COMPLIANCE WILL BE | | | ACHIEVED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|