| Plan Review Notes For Permit 01030013 |
| Permit Number |
01030013 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-03-08 00:00:00 | DENIED | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) DRAWINGS ARE REQUIRED TO BE SIGNED, | | | SEALED AND DATED BY A DESIGN | | | PROFESSIONAL. CITY AMENDMENTS 104.2.3 | | | | | | 4) PROVIDE DRAWINGS/DETAILS INDICATING | | | THAT ADEQUATE FIRE SPRINKLER COVERAGE | | | WILL BE MAINTAINED. | | | | | | 5) PROVIDE 2 CURRENT COMPLETE COPIES OF | | | SBCCI OR METRO DADE PRODUCT APPROVALS | | | FOR: | | | - NEW EXTERIOR SLIDE DOOR UNITS | | | | | | 6) GUARDRAILS ARE REQUIRED AT EXTERIOR | | | OF NEW DOOR UNITS. 97 SBC 1014.1.2 | | | | | | 7) ALL PARTITIONS SHALL BE CONSTRUCTED | | | OF NON-COMBUSTIBLE MATERIALS.97 SBC 609. | | | 2.1 | | | | | | 8) PROVIDE ENERGY CALCULATIONS AS | | | REQUIRED BY 101.2.2 OF THE FLORIDA | | | ENERGY CODE. | | | | | | 9) PROVIDE WALL SECTION OF EXTERIOR WALL | | | THAT IS BEING ENCLOSED INTO CONDITIONED | | | SPACE. INDICATE INSULATION, FURRING, | | | WALL COVERING, ETC. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|