2002-02-28 00:00:00******************UNSAT!****************
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT AND RESUBMIT.
  
 1) THE RISER DIAGRAM SHOWS THREE
 MAINS,THE GEAR ROOM SHOWS TWO,AND THEY
 ARE INCORRECTLY MARKED "1 OF 1" AND "2
 OF 2".
  
 2) AIR HANDLERS 1&3 ARE REVERSED M-1.C
 AND E-1.C. PLEASE CLARIFY.
  
 3) PANEL "P" MUST HAVE A DISCONNECT AS
 PER 225-32. IT IS INDICATED AS "MLO."
 ONTHE PANEL SCHEDULE.
  
 4) PROVIDE A RECEPTACLE FOR CU-A PER
 210-63.
  
 5) NOTE #22 ON SHEET E-2.C REFERS TO A
 NON EXISTENT ARTICLE.
  
 6) THE GROUND WIRES RUNNING FROM THE
 GUTTER TO EACH OF THE MAIN DISCONNECTS
 ARE PROVIDING A PARALLEL GROUND PATH
 WITH THE NEUTRAL CONDUCTOR.
  
 7) WATER HEATER CIRCUIT AT THE UNIT IS
 SHOWN AS COMING OUT OF PANEL "A".
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW