| Plan Review Notes For Permit 01021195 |
| Permit Number |
01021195 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-02-28 00:00:00 | ******************UNSAT!**************** | | | PLEASE NOTE THE FOLLOWING | | | DISCREPANCIES,CORRECT AND RESUBMIT. | | | | | | 1) THE RISER DIAGRAM SHOWS THREE | | | MAINS,THE GEAR ROOM SHOWS TWO,AND THEY | | | ARE INCORRECTLY MARKED "1 OF 1" AND "2 | | | OF 2". | | | | | | 2) AIR HANDLERS 1&3 ARE REVERSED M-1.C | | | AND E-1.C. PLEASE CLARIFY. | | | | | | 3) PANEL "P" MUST HAVE A DISCONNECT AS | | | PER 225-32. IT IS INDICATED AS "MLO." | | | ONTHE PANEL SCHEDULE. | | | | | | 4) PROVIDE A RECEPTACLE FOR CU-A PER | | | 210-63. | | | | | | 5) NOTE #22 ON SHEET E-2.C REFERS TO A | | | NON EXISTENT ARTICLE. | | | | | | 6) THE GROUND WIRES RUNNING FROM THE | | | GUTTER TO EACH OF THE MAIN DISCONNECTS | | | ARE PROVIDING A PARALLEL GROUND PATH | | | WITH THE NEUTRAL CONDUCTOR. | | | | | | 7) WATER HEATER CIRCUIT AT THE UNIT IS | | | SHOWN AS COMING OUT OF PANEL "A". | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 651/ 659-8096 EXT.8392 |
|