Plan Review Notes
Plan Review Notes For Permit 01021195
Permit Number 01021195
Review Stop M
Sequence Number 4
Notes
Date Text
2002-01-30 00:00:00 
  
 PLAN SHEET M-2.C, DETAIL OF AHU -
 CONDENSATE SHALL VENT TO THE ATMOSPHERE
 AS PER COUNTYWIDE AMMENDMENTS 1994 SPC
 804.3 #5.DETAIL DOES NOT INDICATE
 AUXILIARY DRAIN PAN WITH OVER FLOW
 PROTECTION AS REQUIRED PER 1997 SMC
 304.8.6.1.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION TO ALARM/STOBE IN NORMALLY
 OCCUPIED AREAS AS PER 1997 SMC 406.1 &
 NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.