| Plan Review Notes For Permit 01021195 |
| Permit Number |
01021195 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-01-30 00:00:00 | | | | | | | PLAN SHEET M-2.C, DETAIL OF AHU - | | | CONDENSATE SHALL VENT TO THE ATMOSPHERE | | | AS PER COUNTYWIDE AMMENDMENTS 1994 SPC | | | 804.3 #5.DETAIL DOES NOT INDICATE | | | AUXILIARY DRAIN PAN WITH OVER FLOW | | | PROTECTION AS REQUIRED PER 1997 SMC | | | 304.8.6.1. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH | | | NOTIFICATION TO ALARM/STOBE IN NORMALLY | | | OCCUPIED AREAS AS PER 1997 SMC 406.1 & | | | NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|