| Plan Review Notes For Permit 01021195 |
| Permit Number |
01021195 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-01-31 00:00:00 | ****************** UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE THAT THERE WERE | | | NOTES FROM 9/10/01 THAT ASK FOR PLANS | | | TO REFLECT "99" NEC WHICH WE ARE UNDER. | | | ON THE PLANS THERE ARE NOTES ON EACH | | | SHEET THAT REFERENCE "96" NEC. | | | PLEASE CORRECT | | | | | | 2)NOTE: PLEASE NOTE THERE ARE STILL NO | | | CLARIFICATION SHOWN FOR THE REQ`D | | | EQUIPMENT GROUNDING CONDUCTOR BETWEEN | | | MAIN DISCONNETS AND PANELS.SIZE PER | | | 250-122. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE INDICATE ALL CHANGES | | | WITH CLOUDS /TRIANGLES. | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|