| Plan Review Notes For Permit 01021195 |
| Permit Number |
01021195 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-09-05 00:00:00 | 1) PLEASE PROVIDE METHODS FOR PROVIDING | | | A SUITABLE WATER SUPPLY FOR WHEN THE | | | BUILDINGS INCLUDING THE CLUBHOUSE ARE | | | UNDER CONSTRUCTION SHOULD A FIRE OCCUR. | | | THE ARRANGEMENT THAT HAS BEEN PROPOSED | | | USING A DRY HYDRANT AND A 10HP PUMP | | | WILL NOT BE ACCEPTED BY THIS OFFICE. | | | 2) AN EMERGENCY LIGHT FIXTURE IS | | | REQUIRED IN THE RACQUETBALL COURT. | | | 3) ADDITIONAL FIRE EXTINGUISHERS MUST | | | BE PROVIDED TO SATISFY THE MAXIMUM | | | TRAVEL DISTANCE OF 75 FEET. | | | 4) STAIRS ARE TO BE CONSTRUCTED WITH | | | A MINIMUM OF 11" TREADS, MINIUMUM 4"AND | | | MAXIMUM OF 7" RISERS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT 8497 | | | 835-2910 |
|