| Plan Review Notes For Permit 01021195 |
| Permit Number |
01021195 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-07-12 00:00:00 | PLUMBING PLAN REVIEW DENIED,2ND TIME | | | THIS REVIEW FOR,CLUB HOUSE, MAINTENANCE | | | BUILDING, SPA & POOL, PAVILLION ONLY. | | | 1) SHT P-2C AS DISCUSSED PREVIOUSLY,AIR | | | CHAMBERS SERVE NO USEFUL PURPOSE. | | | SPC 94 SEC 607.8.3, LIST TYPE OF WATER | | | HAMMER ARRESTOR THAT IS TO BE USED. | | | (2)SHT P0-1 POOL PAVILLION BAR SINK SHOW | | | ISOMETRIC FOR DWV & WATER PIPING. | | | (3) SHT CH-1 CLUB HOUSE REST RM,DOES NOT | | | MATCH SHT P0-1 REST RM LAYOUT. | | | (4)SHT P-1.C FIXTURE CONNECTION SCHEDULE | | | REFERES TO SFBC, WE ARE USING SPC 94. | | | (5A) SHT MAIN-1 MAINTENANCE RST RM. | | | DOOR IS SWING INTO CLEAR FLR SPACE OF | | | TURNING RADIUS, FACBC 97 SEC 4.22.2(1) | | | (5B) FLOOR DRAIN IN MAINTENANCE ROOM, | | | COMPLY W/SEC 1004.6 SAND TRAP,OR OIL | | | SEPERATOR. SEC 1004.6 | | | (5C) WATER SUPPLY TO FUTURE CAR WASH, | | | SHOW FUTURE SANITARY SEWER CONNECTION. | | | SPC 94 SEC 104.3 | | | END OF COMMENTS, PAUL SCHMITZ | | | QUESTIONS 561-659-8096X 8233 |
|