2001-09-07 00:00:00*******************DENIED***************
  
  
  
 1.AHU #1 THE "CLUB ROOM" SHALL HAVE
 A RETURN AIR FROM THIS AREA.
  
 2.PLAN SHEET M-2.C, NOTE #13 F. STILL
 READS "COMBUSTIBLES IN RETURN AIR
 PLENUM".
  
 3.A/C CLOSET DETAIL STILL HAS THE
 CONDENSATE VENTING INTO THE WALL.
 CONDENSATE SHALL VENT TO THE
 ATMOSPHERE OR A MINIMUM OF 6" ABOVE
 THE INSULATION IN THE ATTIC AREA.
 AMENDED 1994 SPC 804.3 #5.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.