| Plan Review Notes For Permit 01021195 |
| Permit Number |
01021195 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-07 00:00:00 | *******************DENIED*************** | | | | | | | | | | | | 1.AHU #1 THE "CLUB ROOM" SHALL HAVE | | | A RETURN AIR FROM THIS AREA. | | | | | | 2.PLAN SHEET M-2.C, NOTE #13 F. STILL | | | READS "COMBUSTIBLES IN RETURN AIR | | | PLENUM". | | | | | | 3.A/C CLOSET DETAIL STILL HAS THE | | | CONDENSATE VENTING INTO THE WALL. | | | CONDENSATE SHALL VENT TO THE | | | ATMOSPHERE OR A MINIMUM OF 6" ABOVE | | | THE INSULATION IN THE ATTIC AREA. | | | AMENDED 1994 SPC 804.3 #5. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|