| Plan Review Notes For Permit 01021195 |
| Permit Number |
01021195 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-10 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS FOR SITE | | | LIGHTING UNDER DIFFERENT # WAS SUBMITTED | | | WITH CLUB HOUSE PLANS AND NOTES FROM | | | THESE PLANS WERE ON SITE# ALSO. | | | | | | 2)NOTE: PLEASE NOTE CODE ARTS NOTED ON | | | PLANS REF. "96" NEC. NEED TO SHOW "99" | | | NEC. PLEASE NOTE GROUNDING ELECTRODE TO | | | BE SHOWN TO COLD WATER AND BLDG STEEL | | | PER 250-66. | | | PLEASE NOTE CLEARENCES IN NOTES, ARE | | | SHOWN PER 110-16. '99' IS 110-26. | | | | | | 3)NOTE: PLEASE NOTE THAT NOTE FROM FIRST | | | REVIEW NEEDS CLARIFICATION ON EQUIPMENT | | | GROUNDING METHOD BETWEEN FIRST MEANS OF | | | DISCONNECT AND PANELS. PER 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|