2001-04-08 00:00:00PLUMBING PLAN REVIEW DENIED
 REFERENCES SPC 94,SBC 97, FAIR HOUSING
 ACT 1998 REVISED EDITION, FACBC-97.
 (1A) CLUBHOUSE PAVILLION PLANS,DO NOT
 MATCH CLUBHOUSE AMENITY PLANS, ALSO
 SHTS T-A1, TRASH ENCLOSURE STRUCTURE.
 PROVIDE MINIMUM OF 2 COMPLETE SETS OF
 PLANS. SEC.104.3
 (1B) PROVIDE MINIMUM 2 SETS OF CIVIL
 PLANS. SEC 104.3
 (2) SHT P-1C DRINKING FOUNTAINFACBC 97
 SEC 4.1.3(10)(A) PROVISIONS FOR PEOPLE
 WHO HAVE TROUBLE BENDING OR STOOPING.
 (3) SHT P-2C AIR CHAMBERS TO COMPLY WITH
 SEC 607.8.3 ACCESSIBLE,RECHARGEABLE.
 (4) SHT CH-1 DOES NOT MATCH, SHT P-1C,
 URINAL,LAVATORY NOT SHOWN.SEC 104.3
 (5) SHT CH-1 PROVIDE CALCULATIONS FOR
 MINIMUM FACILITIES,TAB 407.
 (6) SHT GH-1 PROVIDE ISOMETRIC DRAWINGS
 OF DWV & WATER PIPE,WITH PIPE SIZES,
 SEC 104.3
 (7A)SHTS M-A1/MAIN.1 H/C,W/C TO BE 18"
 OFF THE WALL, FACBC FIG 28.
 (7B) REST RM DOOR SWINGS INTO TURNING
 RADIUS. FACBC 4.22.2(1).
 (7C) FLOOR DRAIN & FUTURE CAR WASH DRAIN
 AT THE MAINTENANCE GARAGE TO RUN THRU A
 OIL & SAND SEPERATOR.SEC 1004.
 (8) SHT P-101 BUILDING TYPES I,II,III,IV
 COMPLY WITH SEC 710.2.4 BLDG DRAIN CO'S
 (9) SHT P-105 CONDENSATE DRAINS,
 MECHANICAL PLAN REVIEW TO ADDRESS
 PERFORATED CAPS.
 (10) SHT P-105 WATER HEATER PAN DRAINS
 SEC 507.8.2,MINIMUM SIZE 1".
 (11) SHT P-105 BUILDINGS I,II,III,IV
 U/G SANITARY DIAGRAM,COMPLY WITH TAB
 714.1 FOOT NOTE #3, NOT OVER 2 WATER
 CLOSETS ON 3" DRAIN LINE.
 (12) SHT P-1 BACK FLOW PREVENTERS
 REQUIRED ON DOMESTIC WATER TO EA. BLDG.
 LOCAL ORDINANCE # 2938-96.
 (13) SHT P-302 VTR,SBC 704.4.2
 COMBUSTIBLE MATERIALS,NOT PERMITED TO
 PENETRATE FIRE RATED ROOF ASSEMBLY.
 (14)SHT A-5.6 TYPICAL OF ALL TYPES AND
 MODELS,COMPLY WITH FAIR HOUSING ACT
 DESIGN MANUAL REVISED EDITION 1998,
 REGULATION 24,CODE OF FEDERAL REGULATION
 (CFR) 100.205(C)(3)(IV).
 PROVIDE SEPERATE PLANS SPECIFICALLY FOR
 FAIR HOUSING ACT COMPLIANCE, SHOWING AS
 ILLUSTRATED IN THE FAIR HOUSING ACT
 MANUAL,FOR EACH TYPE AND MODEL.
 SHOW DIMENSION,MANEUVERING & CLEAR
 FLOOR SPACE.
 END OF COMMENTS,PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233