| Plan Review Notes For Permit 01021195 |
| Permit Number |
01021195 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-06 00:00:00 | ******************DENIED**************** | | | | | | CLUBHOUSEPERMIT 01021195 | | | | | | | | | 1.DRAWING NUMBER M-1.C IN THE NOTES, | | | 13. F. THERE SHALL BE NO COM- | | | BUSTIBLES IN THE RETURN AIR PLENUM | | | AS PER 1997 SMC 609.1.1. | | | | | | 2.AHU #2 NEEDSRETURN AIR TO THE | | | "KIDS FUN CENTER". | | | | | | 3.AHU #1 NEEDS A RETURN AIR TO THE | | | "RECEPTION" AREA AS WELL AS THE | | | "CLUBROOM". | | | | | | 4.NOTE: PROVIDE DUCT MOUNTED SMOKE | | | DETECTOR FOR FAN SHUTDOWN WITH | | | NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS, AS PER | | | NFPA 90A 4-4.4.3. |
|