Plan Review Notes
Plan Review Notes For Permit 01021195
Permit Number 01021195
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-04-05 00:00:001) PROVIDE SEPARATE PLANS AND PERMITS
 FOR ENTRY GATES. ENTRY GATES TO BE AT
 LEAST 20 FEET IN CLEAR WIDTH AND BE
 EQUIPPED WITH BATTERY BACK-UP FEATURE
 WHEN LOSS OF POWER OCCURS. ALL ROADS
 USED BY FIRE AND PARAMEDICAL UNITS
 MUST BE ABLE TO SUPPORT THE WEIGHTS
 OF THESE APPARATUS.
 2) PLEASE BE ADVISED THAT ALL BUILDINGS
 THREE OR MORE STORIES IN HEIGHT
 REGARDLESS OF OCCUPANCY TYPE SHALL BE
 FIRE SPRINKLER PROTECTED IN ACCORDANCE
 WITH FS 553.895(2) FIRE SPRINKLER
 DRAWINGS AND HYDRAULIC CALCULATIONS ARE
 TO BE PROVIDED WITH PERMIT DRAWINGS.
 3) BUILDING ADDRESSES REQUIRED ON ALL
 BUILDINGS PER CITY CODE REQUIREMENTS.
 4) ALL CANVAS CANOPIES TO BE FIRE
 RETARDANT.
 5) ALL FIRE SPRINKLER SYSTEMS AND FIRE
 ALARM SYSTEMS TO BE MONITORED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 6) PLEASE PROVIDE SEPARATE PLANS AND
 PERMITS FOR FOR FIRE ALARM SYSTEMS. FIRE
 ALARM SYSTEMS TO BE CLASS A OR FULLY
 ADDRESSABLE. CUT SHEETS, WIRING DIAGRAMS
 AND BATTERY CALCULATIONS ARE TO BE
 PROVIDED.
 7) SMOKE DETECTORS WITHIN UNITS TO BE
 ELECTRIC AND TO BE A MINIMUM OF THREE
 FEET FROM AIR CONDITIONER DIFFUSERS.
 8) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS IN THE
 CLUBHOUSE.
 9) ANY CHANGES IN ELEVATIONS LESS THAN
 21 INCHES SHALL BE BY RAMPS NEAR POOL.
 STEPS WHEN INSTALLED SHALL BE A MINIMUM
 OF THREE AT 7 INCHES EACH.
 10) PLEASE PROVIDE INTERIOR FINISH FOR
 WALLS AND CEILINGS IN CLUBHOUSE.
 11) PLEASE PROVIDE HYDRANT LOCATIONS AND
 WATER MAIN SIZES. HYDRANTS SHALL MEET
 UTILITY AND FIRE RESCUE REQUIREMENTS AND
 SHALL BE SPACED BETWEEN 300-500 FEET
 APART.
 12) PLEASE PROVIDE WINDOW INFORMATION
 BY STAIRWAY FOR TYPE 1 BUILDINGS.
 13) PLEASE PROVIDE INFORMATION ON
 BEDROOM WINDOWS FOR TYPE 1 BUILDINGS.
 14) PLEASE PROVIDE INTERIOR FINISH FOR
 TYPE 1 BUILDINGS.
 15) PLEASE PROVIDE BRIDGE WIDTH AND
 WEIGHT LIMITATIONS.
 16) IS GAURD BOOTH STAFFED 24 HOURS A
 DAY.
 17) ALL APARTMENT BUILDINGS TO COMPLY
 WITH NFPA 101, THE LIFE SAFETY CODE,
 1985 EDITION, SECTION 18.
 18) STAIRS TO COMPLY WITH NEW STAIR
 REQUIREMENTS OF NFPA 101, THE LIFE
 SAFETY CODE, 1985 EDITION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910