| Date |
Text |
| 2001-04-05 00:00:00 | 1) PROVIDE SEPARATE PLANS AND PERMITS |
| | FOR ENTRY GATES. ENTRY GATES TO BE AT |
| | LEAST 20 FEET IN CLEAR WIDTH AND BE |
| | EQUIPPED WITH BATTERY BACK-UP FEATURE |
| | WHEN LOSS OF POWER OCCURS. ALL ROADS |
| | USED BY FIRE AND PARAMEDICAL UNITS |
| | MUST BE ABLE TO SUPPORT THE WEIGHTS |
| | OF THESE APPARATUS. |
| | 2) PLEASE BE ADVISED THAT ALL BUILDINGS |
| | THREE OR MORE STORIES IN HEIGHT |
| | REGARDLESS OF OCCUPANCY TYPE SHALL BE |
| | FIRE SPRINKLER PROTECTED IN ACCORDANCE |
| | WITH FS 553.895(2) FIRE SPRINKLER |
| | DRAWINGS AND HYDRAULIC CALCULATIONS ARE |
| | TO BE PROVIDED WITH PERMIT DRAWINGS. |
| | 3) BUILDING ADDRESSES REQUIRED ON ALL |
| | BUILDINGS PER CITY CODE REQUIREMENTS. |
| | 4) ALL CANVAS CANOPIES TO BE FIRE |
| | RETARDANT. |
| | 5) ALL FIRE SPRINKLER SYSTEMS AND FIRE |
| | ALARM SYSTEMS TO BE MONITORED BY A |
| | LICENSED UL LISTED CENTRAL STATION |
| | APPROVED BY THE FIRE RESCUE DEPARTMENT. |
| | 6) PLEASE PROVIDE SEPARATE PLANS AND |
| | PERMITS FOR FOR FIRE ALARM SYSTEMS. FIRE |
| | ALARM SYSTEMS TO BE CLASS A OR FULLY |
| | ADDRESSABLE. CUT SHEETS, WIRING DIAGRAMS |
| | AND BATTERY CALCULATIONS ARE TO BE |
| | PROVIDED. |
| | 7) SMOKE DETECTORS WITHIN UNITS TO BE |
| | ELECTRIC AND TO BE A MINIMUM OF THREE |
| | FEET FROM AIR CONDITIONER DIFFUSERS. |
| | 8) PROVISIONS ARE TO BE MADE FOR AT |
| | LEAST TWO HANDICAPPED PERSONS IN THE |
| | CLUBHOUSE. |
| | 9) ANY CHANGES IN ELEVATIONS LESS THAN |
| | 21 INCHES SHALL BE BY RAMPS NEAR POOL. |
| | STEPS WHEN INSTALLED SHALL BE A MINIMUM |
| | OF THREE AT 7 INCHES EACH. |
| | 10) PLEASE PROVIDE INTERIOR FINISH FOR |
| | WALLS AND CEILINGS IN CLUBHOUSE. |
| | 11) PLEASE PROVIDE HYDRANT LOCATIONS AND |
| | WATER MAIN SIZES. HYDRANTS SHALL MEET |
| | UTILITY AND FIRE RESCUE REQUIREMENTS AND |
| | SHALL BE SPACED BETWEEN 300-500 FEET |
| | APART. |
| | 12) PLEASE PROVIDE WINDOW INFORMATION |
| | BY STAIRWAY FOR TYPE 1 BUILDINGS. |
| | 13) PLEASE PROVIDE INFORMATION ON |
| | BEDROOM WINDOWS FOR TYPE 1 BUILDINGS. |
| | 14) PLEASE PROVIDE INTERIOR FINISH FOR |
| | TYPE 1 BUILDINGS. |
| | 15) PLEASE PROVIDE BRIDGE WIDTH AND |
| | WEIGHT LIMITATIONS. |
| | 16) IS GAURD BOOTH STAFFED 24 HOURS A |
| | DAY. |
| | 17) ALL APARTMENT BUILDINGS TO COMPLY |
| | WITH NFPA 101, THE LIFE SAFETY CODE, |
| | 1985 EDITION, SECTION 18. |
| | 18) STAIRS TO COMPLY WITH NEW STAIR |
| | REQUIREMENTS OF NFPA 101, THE LIFE |
| | SAFETY CODE, 1985 EDITION. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |