Date Text
2001-03-17 00:00:00SAN MARINO APARTMENT COMPLEX
 AT BEAR LAKES
 4330 N MILITARY TRAIL
 PLAN REVIEW
 ARCHITECT: MOURIZ SALAZAR
 PHONE- (305) 273-9911
 FAZ-(305) 273-9424
 PROJECT MANAGER: EDDIE PEREZ
  
 THE FIRST COMMEENTS WILL BE GENERIC COM-
 MENTS THAT MAY PRETAIN TO THE PROJECT OR
 TO ALL THE BUILDINGS IN THE PROJECT.
  
 1)- 104.2.2 ADMINISTRATIVE CODE: A
 SURVEY WILL BE REQUIRED FOR THE PROJECT.
 THE CITY IS DETERMINING THE SITE ADDRESS
 ONE OF THE QUESTIONS WE ASKED MR. PEREZ
 IS IF THIS PROJECT HAS ACTUAL FRONTAGE
 ON MILITARY TRAIL? MR. PEREZ STATED THAT
 THERE IS A SECOND PHASE THAT WILL TAKE
 PLACE IN PARCEL"K". THIS SECOND PARCEL
 WILL IT HAVE THE SAME APARTMENT COMPLEX
 NAME, PARCEL CONTROL NUMBER, AND WILL
 THE BUILDING SEQUENCE NUMBERING SYSTEM
 BE A CONTINUATION OF THE PRESENT SYSTEM?
 THERE IS ALSO A NEW SIDE STREET THAT
 WILL BE CUT IN, WILL THIS BE A PRIVATE
 STREET OR WILL THIS BE A ACTUAL CITY
 STREET & WOULD YOUR CLIANT PREFER THE
 ADDRESS BE OFF OF THIS SIDE STREET?
  
 2)- THE SITE PARCEL"I" IS PARTIALLY
 LOCATED IN A "A-8" FLOOD ZONE WITH THE
 BASE FLOOD ELEVATION LOCATED AT 16'-0".
 THE CITY CODE REQUIRES THAT ALL RESIDENT
 IAL CONSTRUCTION SHALL HAVE THELOWEST
 FLOOR LEVEL 6" ABOVE THE BASE FLOOD ELEV
 ATION,FOR NONRESIDENTIAL CONSTRUCTION,
 SHALL HAVE EITHER HAVE THE LOWEST FLOOR
 ELEVATED 6" ABOVE THE BASE FLOOD ELEVA-
 TION OR, TOGETHER WITH ATTENDANT UTILITY
 & SANITARY FACILITIES, BE FLOODPROOFED
 SO THAT BELOW 6" ABOVE THE FLOOD BASE
 LEVEL THE STRUCTURE IS WATERTIGHT, WITH
 WALLS SUBSTANTIALLY IMPERMEABLE TO THE
 PASSAGE OF WATER AND WITH THE STRUCTURE
 COMPONENTS HAVING THE CAPACITY OF RESIST
 ING HYDROSTATIC & HYDRODYNAMIC LOADS AND
 THE EFFECTS OF BUOYANCY. A REGISTERED
 PROFESSIONAL ENGINEER OR ARCHITECT SHALL
 CERTIFY THAT THE STANDARDS OF THIS SUB-
 SECTION ARE SATISFIED. SUCH CERTIFICA-
 TION SHALL BE PROVIDED TO THE CITY ENGIN
 EER.
  
 3)- THIS PROJECT QUALIFIES TO COMPLY
 WITH THE PROVISIONS OF SECTION 105.3,
 RESIDENT INSPECTOR, THE CITY OF WEST
 PALM BEACH 1997 COUNTYWIDE ADMINISTRA-
 TION CODE & CHAPTER 468,PART XII
 FLORIDA STATUTE.TO REGISTER CONTACT
 ASSISTANT BUILDING OFFICIAL DON NEELY
 BEFORE THE PERMIT CAN BE ISSUED.
  
 4)- 1804.2.7 COUNTYWIDE AMENDMENTS:
 SOIL TEST, INFORMATION REQUIRED AND THE
 FREQUENCY OF TESTING REQUIRED. SEE
 ATTACHMENT.
  
 5)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 A): INCICATE POSITIVE & NEGITIVE WIND
 PRESSURES (INCLUDING END ZONES)
 FOR ALL GLAZED OPENINGS, DOORS AS
 WELL AS GARAGE DOORS.
 B): SBC 1704 EXTERIOR WINDOW & DOOR
 ASSEMBLIES: TEST REPORTS ARE TO IN-
 DICATE THE WINDOWS PRESSURE IS TEST
 ED FOR A PERIOD OF TIME, A 10 SEC-
 OND PERIOD AT A LOAD EQUAL TO 1.5
 TIMES THE DESIGN PRESSURE. SBCCI
 REPORTS AND DADE COUNTY REPORTS ARE
 ACCEPTED. ALL PRODUCTS SHALL BEAR
 THE LABEL VERIFYING CERTIFICATION
 & INDICATING THE DESIGN PRESSURE
 RATING.
 C): 1606.4/1707.4.1 COUNTYWIDE AMEND.
 GLAZED OPENINGS REQUIRE LARGE MIS-
 SLE IMPACT RESISTANCE TESTING, SEE
 COPY OF POLICY & PROCEDURE FOR
 IMPLEMENTATION OF HURRICANE MISSLE
 IMPACT PROTECTION STANDARDS.NOTE #
 14 IN REGARDS TO LARGE OR MULTI-
 STORY PROJECTS.
 D): ROOF COVERINGS 1503.3.2 ROOF COVER-
 INGS AND SYSTEMS SHALL BE DESIGNED
 TO WITHSTAND WINDLOADS PRESCRIBED
 IN CHAP. 16/ 110 MPH WINDZONE.
 1707.5 TESTING FOR CLAY/ CEMENT
 TILE, SBCCI OR DADE COUNTY ACCEPT-
 ANCE REPORT ARE ACCEPTED.
  
 6)- FAIR HOUSING ACT: CHAP.6- THE PLANS
 FOR BACKING FOR THE REAR WALL INDICATES
 BACKING TO BE PLACED A MAX.32" WHICH IS
 THE MINIMUM, THE PLANS ARE MISSING BACK-
 ING BEHIND THE WATER CLOSETS AS DEPICTED
 FOR NO SIDE WALLS ADJACENT TO THE WATER
 CLOSET. THE PLANS INDICATE A 1/2" RISE
 AT ALL ENTRY DOORS BUT THE QUALIFIER
 A 2/1 RATIO FOR CHANGE OF GRADE SHOULD
 BE ADDED. SEE ATTACHMENTS.
  
 7)- 104.2.2 ADDITIONAL INFO: WILL THE
 ROOF BE INSTALLED WITH 19/32" PLYWOOD OR
 WILL 5/8" PLYWOOD BE USED AS THE PLANS
 INDICATE?
  
  
 CLUBHOUSE
 1)- SHEET CH-7 UNDER GENERAL NOTES #8 IN
 DICATE PRE-FABRICATED TRUSSES -WIND
 UPLIFT: CORRECT TO: COMPUTED TO THE
 STANDARD BUILDING CODE, ASCE 7-95.
  
 2)- FRONT ENTRY HAS NO RAMPAGE FOR HANDI
 CAPPED INDIVIDUALS, FAIR HOUSING ACT,
 FL. ACCESIBILITY CODES.
  
 3)-DISCREPANCY: SHEET CH3 REAR ELEVATION
 THE COVERED WALKWAY ADJACENT TO THE
 EXERCISE ROOM, VISUALLY INDICATES STAIRS
 WHILE THERE IS A NOTE "RAMP", SHEET CH-4
 ALSO DEPICTS STAIRS, PO-1 ALSO DEPICTS
 STAIRSWITH A NOTE "RAMP".
  
 4)- SHEET CH-5 SEC-B:
 A): DEPICTS A DROPPED CEILING ATTACHED
 TO 6" STEEL FURRING ATTACHED TO THE
 BOTTOM OF THE TRUSSES, WHAT TYPE OF
 FASTENER WILL BE USED TO TRANSFER
 THE CEILING LOADS TO THE TRUSSES?
 B): THIS SAME DETAIL DEPICTS A PLEXI-
 GLASS PANEL WALL & 12'-0+" WALL
 ABOVE, HOW IS THIS SUPPORTED?
  
 BUILDING PLAN REVIEW