| 2001-07-11 00:00:00 | *******************PROVISO************** |
| | |
| | TYPE III |
| | |
| | NOTHING ON PLANS HAVE CHANGED. |
| | |
| | |
| | PLEASE TAKE NOTE TO THE FOLLOWING ISSUES |
| | |
| | 1.AS STATED IN REVIEW NOTES DATED |
| | 6/5/01, PLAN M-306 DETAIL OF A/C |
| | CLOSET, PROVIDE OVERFLOW PAN FOR |
| | UPPER FLOORS ONLY....OVERFLOW PAN |
| | SHALL GO ON EVERY FLOOR TO PREVENT |
| | DAMAGE TO CARPET, WALLS AND INTERIOR |
| | OF APARTMENT. |
| | |
| | 2.AS DISCUSSED IN MEETING WITH CARLOS |
| | AT CITY HALL, AS PER AMENDED 1997 |
| | SPC 804.3, #5. CONDENSATE DRAINS |
| | SHALL VENT TO ATMOSPHERE, IT SHALL |
| | NOT VENT INTO THE WALL AS SHOWN ON |
| | THE DETAIL.SHOULD TERMINATION BE |
| | IN THE ATTIC, IT SHALL BE A MINIMUM |
| | OF 6" ABOVE THE INSULATION. |
| | |
| | PLEASE REMOVE/CORRECT NOTES THAT REFER |
| | TO DETAILS ON PLANS THAT ARE NOT IN THE |
| | PLAN SET OR HAVE BEEN SHOWN ON |
| | DIFFERENT PLAN (EXAMPLE:SHAFT |
| | ENCLOSURE IS SAID TO BE ON |
| | ARCHITECTURAL PLAN SHEET A-13 #25). |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 EXT. |
| | 8388. |