Plan Review Notes
Plan Review Notes For Permit 01021194
Permit Number 01021194
Review Stop E
Sequence Number 2
Notes
Date Text
2001-07-12 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT OUT OF THREE
 SETS ON TYPE III BUILDING. TWO SETS
 HAVE THE HANDWRITTEN CHANGE OF SERVICE
 WIRE SIZE AND THE 3RD SET HAS NO CHANGE
 AT ALL. PLEASE NOTE THAT ALL CHANGES
 MUST BE SIGNED AND DATED BY THE ENGINEER
 OF RECORD. FS, FAC 471.025
  
 2)NOTE: PLEASE ALSO NOTE THAT THE WIRE
 SIZE INCREASE IS NOT LARGE ENOUGH.
 PER 110-14-C AND 240-3-C. .
 PLEASE SEE 310-16 75` COLUMN.
  
 PLEASE MAKE THE ABOVE CHANGES TO MEET
 NEC. PLEASE SUBMIT THE ABOVE FOR REVIEW
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372