| Plan Review Notes For Permit 01021189 |
| Permit Number |
01021189 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | 1) THE WATER SUPPLY ISSUE FOR FIRE | | | HYDRANTS DURING CONSTRUCTION HAS NOT | | | BEEN RESOLVED. A WATER MAIN EXTENSION | | | HAS TO BE DONE AND THE DEVELOPER HAS | | | ALTERNATE IDEAS TO ADDRESS THIS ISSUE. | | | A LETTER IS TO BE PROVIDED TO THIS | | | OFFICE. | | | 2) NOTE ON PAGE A-1.2. INDICATES | | | BUILDING WILL NOT BE SPRINKLERED. THIS | | | IS NOT CORRECT. | | | 3) STORAGE NOT PERMITTED UNDERNEATH | | | EXIT STAIRS. STORAGE AREA MUST BE | | | RATED SAME AS THE SATIR. | | | 4) HOW IS DRYER VENT EXHAUST RISER | | | CLEANED OF COMBUSTIBLE LINT. | | | 5) HOW ARE THE OUTER EXIT STAIRS BEING | | | ILLUMINATED SHOULD THE POWER BE LOST. | | | 6) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 7) FIRE ALARM RISER SHOWS E.O.L.'S. ONLY | | | CLASS A OR FULLY ADDRESSABLE FIRE ALARM | | | SYSTEMS ARE PERMITTED. | | | 8) PROVIDE MORE DETAILS FOR EGRESS | | | WINDOWS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|