Plan Review Notes
Plan Review Notes For Permit 01021189
Permit Number 01021189
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:001) THE WATER SUPPLY ISSUE FOR FIRE
 HYDRANTS DURING CONSTRUCTION HAS NOT
 BEEN RESOLVED. A WATER MAIN EXTENSION
 HAS TO BE DONE AND THE DEVELOPER HAS
 ALTERNATE IDEAS TO ADDRESS THIS ISSUE.
 A LETTER IS TO BE PROVIDED TO THIS
 OFFICE.
 2) NOTE ON PAGE A-1.2. INDICATES
 BUILDING WILL NOT BE SPRINKLERED. THIS
 IS NOT CORRECT.
 3) STORAGE NOT PERMITTED UNDERNEATH
 EXIT STAIRS. STORAGE AREA MUST BE
 RATED SAME AS THE SATIR.
 4) HOW IS DRYER VENT EXHAUST RISER
 CLEANED OF COMBUSTIBLE LINT.
 5) HOW ARE THE OUTER EXIT STAIRS BEING
 ILLUMINATED SHOULD THE POWER BE LOST.
 6) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 7) FIRE ALARM RISER SHOWS E.O.L.'S. ONLY
 CLASS A OR FULLY ADDRESSABLE FIRE ALARM
 SYSTEMS ARE PERMITTED.
 8) PROVIDE MORE DETAILS FOR EGRESS
 WINDOWS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910