Plan Review Notes
Plan Review Notes For Permit 01021181
Permit Number 01021181
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:001) WATER SUPPLY FOR FIRE HYDRANTS WHEN
 THE BUILDINGS ARE UNDER CONSTRUCTION
 HAS NOT BEEN RESOLVED. THE DEVELOPER
 HAS PROPOSED ALTERNATIVES SINCE A
 WATER MAIN EXTENSION MUST OCCUR. THIS
 ISSUE REMAINS UNRESOLVED.
 2) NOTE ON A-1.4. INDICATES THAT NO
 FIRE SPRINKLER SYSTEM WILL BE PRESENT.
 THIS IS NOT CORRECT.
 3) STORAGE NOT PERMITTED UNDERNEATH
 STAIRS. STORAGE AREAS MUST BE RATED
 THE SAME AS THE STAIRS.
 4) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 5) FIRE ALARM RISER SHOWS E.O.L.'S.
 ONLY CLASS A OR FULLY ADDRESSABLE FIRE
 ALARM SYSTEMS WILL PER PERMITTED.
 6) HOW IS COMBUSTIBLE LINT REMOVED FROM
 THE DRYER EXHAUST RISERS.
 7) PROVIDE MORE DETAILS ON EGRESS
 WINDOWS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910