| Plan Review Notes For Permit 01021181 |
| Permit Number |
01021181 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | 1) WATER SUPPLY FOR FIRE HYDRANTS WHEN | | | THE BUILDINGS ARE UNDER CONSTRUCTION | | | HAS NOT BEEN RESOLVED. THE DEVELOPER | | | HAS PROPOSED ALTERNATIVES SINCE A | | | WATER MAIN EXTENSION MUST OCCUR. THIS | | | ISSUE REMAINS UNRESOLVED. | | | 2) NOTE ON A-1.4. INDICATES THAT NO | | | FIRE SPRINKLER SYSTEM WILL BE PRESENT. | | | THIS IS NOT CORRECT. | | | 3) STORAGE NOT PERMITTED UNDERNEATH | | | STAIRS. STORAGE AREAS MUST BE RATED | | | THE SAME AS THE STAIRS. | | | 4) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 5) FIRE ALARM RISER SHOWS E.O.L.'S. | | | ONLY CLASS A OR FULLY ADDRESSABLE FIRE | | | ALARM SYSTEMS WILL PER PERMITTED. | | | 6) HOW IS COMBUSTIBLE LINT REMOVED FROM | | | THE DRYER EXHAUST RISERS. | | | 7) PROVIDE MORE DETAILS ON EGRESS | | | WINDOWS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|