| 2002-01-30 00:00:00 | *******************DENIED*************** | | | | | | | | | PREVIOUS COMMENTS NEVER ADDRESSED. | | | | | | PLAN SHEET M-204 NOTES:#4 1, | | | "VENTILATION SHAFT (NOT A FIRE RATED | | | CHASE)". | | | | | | DUCTS PENETRATING MORE THAN 1 FLOOR | | | SHALL BE PROTECTED BY A SHAFT ENCLOSURE | | | AS PER 1997 SMC 610.4 & NFPA 90A 3-3.4. | | | 1 HOUR RATING FOR BUILDINGS LESS THAN 4 | | | STORIES AND 2 HOUR RATING FOR 4 STORIES | | | AND MORE IN HEIGHT. | | | | | | THE ABOVE ISSUE WAS DISCUSSED IN A | | | MEETING ON JANUARY18, 2002.PLEASE | | | SEE ATTACHED LETTER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|