Plan Review Notes
Plan Review Notes For Permit 01021178
Permit Number 01021178
Review Stop M
Sequence Number 6
Notes
Date Text
2002-01-30 00:00:00*******************DENIED***************
  
  
 PREVIOUS COMMENTS NEVER ADDRESSED.
  
 PLAN SHEET M-204 NOTES:#4 1,
 "VENTILATION SHAFT (NOT A FIRE RATED
 CHASE)".
  
 DUCTS PENETRATING MORE THAN 1 FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 AS PER 1997 SMC 610.4 & NFPA 90A 3-3.4.
 1 HOUR RATING FOR BUILDINGS LESS THAN 4
 STORIES AND 2 HOUR RATING FOR 4 STORIES
 AND MORE IN HEIGHT.
  
 THE ABOVE ISSUE WAS DISCUSSED IN A
 MEETING ON JANUARY18, 2002.PLEASE
 SEE ATTACHED LETTER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.